| Plan Review Notes For Permit 15020886 |
| Permit Number |
15020886 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-03 10:42:33 | PROVIDE MANUFACTURER PRODUCT APPROVALS ON SITE FOR THE | | | INSPECTOR. NEC 110.3(B) | | | VERIFY NEW LOAD DOES NOT EXCEED CAPACITY OF EXISTING | | | ELECTRICAL PANEL AND/OR SERVICE. | | | VERIFY NEW EQUIPMENT VOLTAGE IS CONSISTANT WITH | | | EXISTING SYSTEM VOLTAGE. |
|