| 2015-03-17 15:26:20 | REVISION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- WINDOW SIZES (5'-0" X 4'-0") SPECIFIED ON PLANS FOR |
| | BEDROOMS #3 AND #4 DON'T COMPLY WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310 OF 2010 FBC-RESIDENTIAL. |
| | WINDOWS INFORMATION SUBMITTED IS FOR A WINDOW SIZE |
| | DIFFERENT THAN THE ONE SPECIFIED BY THE ARCHITECT. |
| | REVISE PLANS TO SHOW THE CORRECT SIZE THAT MEETS EGRESS |
| | REQUIREMENTS. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 2- REVISE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. A) INFORMATION SHOWN ON ENERGY |
| | CALCULATIONS DOESN'T MATCH A/C INFORMATION SUBMITTED. |
| | COORDINATE ALL THE INFORMATION WITH A/C PLANS AND A/C |
| | EQUIPMENT SIZING CALCULATIONS. SEE NUMBER OF A/C UNITS. |
| | B) PROVIDE INFORMATION FOR THE ADDITIONAL COOLING AND |
| | HEATING SYSTEMS. WHERE ARE THE DETAILS SPECIFIED ON |
| | ITEM #12 AND #13?. C) SPACES COLUMN ON PAGE 2 OF 6 |
| | SPECIFIES HEATING FOR THE GARAGE, BUT NOT COOLING. |
| | CLARIFY?. C) PROVIDE COMPLETE DETAILED INFORMATION |
| | IDENTIFYING EACH INSULATED DOOR AND WOOD DOOR TAKEN |
| | INTO CONSIDERATION ON PAGE 3 OF 6. SEE PLANS AND |
| | PRODUCT APPROVALS SUBMITTED. SEC. 405.4.3 AND SEC. |
| | 405.5.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 3- TOTAL NUMBER OF ITEMS SUBMITTED IS THREE. THE |
| | REVISION FEE BALANCE IS $103.00. |
| | |