Plan Review Notes
Plan Review Notes For Permit 15020873
Permit Number 15020873
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-17 15:26:20REVISION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- WINDOW SIZES (5'-0" X 4'-0") SPECIFIED ON PLANS FOR
 BEDROOMS #3 AND #4 DON'T COMPLY WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 OF 2010 FBC-RESIDENTIAL.
 WINDOWS INFORMATION SUBMITTED IS FOR A WINDOW SIZE
 DIFFERENT THAN THE ONE SPECIFIED BY THE ARCHITECT.
 REVISE PLANS TO SHOW THE CORRECT SIZE THAT MEETS EGRESS
 REQUIREMENTS. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- REVISE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION. A) INFORMATION SHOWN ON ENERGY
 CALCULATIONS DOESN'T MATCH A/C INFORMATION SUBMITTED.
 COORDINATE ALL THE INFORMATION WITH A/C PLANS AND A/C
 EQUIPMENT SIZING CALCULATIONS. SEE NUMBER OF A/C UNITS.
 B) PROVIDE INFORMATION FOR THE ADDITIONAL COOLING AND
 HEATING SYSTEMS. WHERE ARE THE DETAILS SPECIFIED ON
 ITEM #12 AND #13?. C) SPACES COLUMN ON PAGE 2 OF 6
 SPECIFIES HEATING FOR THE GARAGE, BUT NOT COOLING.
 CLARIFY?. C) PROVIDE COMPLETE DETAILED INFORMATION
 IDENTIFYING EACH INSULATED DOOR AND WOOD DOOR TAKEN
 INTO CONSIDERATION ON PAGE 3 OF 6. SEE PLANS AND
 PRODUCT APPROVALS SUBMITTED. SEC. 405.4.3 AND SEC.
 405.5.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- TOTAL NUMBER OF ITEMS SUBMITTED IS THREE. THE
 REVISION FEE BALANCE IS $103.00.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712