Plan Review Notes
Plan Review Notes For Permit 15020870
Permit Number 15020870
Review Stop G
Sequence Number 1
Notes
Date Text
2015-03-01 07:36:001) SUBMIT MANFACTURING SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. THE ONLY SPECS ON FILE WITH THE CITY ARE FOR
 THE FIREPLACE AND THE BBQ GRIL UNDER PERMIT
 #14020415.L. ALL APPLIANCES SHALL BE LISTED AND LABELED
 PER THE 2010 FUEL GAS CODE SEC.301.3.
 2) SHOW THE TOTAL BTU LOAD ON THE SYSTEM.WPB AMEND. TO
 2010 FBC SEC.107.2.1.107.3.5.3.
 3) SHOW THE DISTANCE FROM THE METER TO THE MOST REMOTE
 OUTLET ON THE SYSTEM. 2010 FGC SEC.402.4.1.
 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 APPLIANCES ON THE INTERIOR OF THE BUILDING.2010 FGC
 SEC. 304.
 5) SUBMIT A PLAN SHOWING THE LOCATION OF ALL GAS
 APPLIANCES. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 6) SUBMIT A PLAN SHOWING HE TYPE, LOCATION, SIZE AND
 TERMINATION POINTS OF ALL THE GAS VENTS.2010 FGC
 SECS.502 THROUGH 505.
 7) THE GAS DRAWING SHOWS PE PIPE TO THE FIRE PIT. PE
 PIPE CAN ONLY BE USED OUTSIDE UNDERGROUND. SUBMIT
 INFORMATION FOR THE ABOVE GROUND PIPE. (MATERIAL &
 SIZE).WPB AMEND. TO 2010 FBC SEC.107.2.1, 2010 FGC
 SEC.404.15.
 8) SHOW THE TYPE OF PIPE MATERIAL FOR THE CONNECTIONS
 AT THE WATER HEATERS, FUTURE DRYER, BBQ, AND THE
 GENERATOR.
 9) INDICATE THE PIPE SIZE OF THE PIPE SECTION BETWEEN
 THE METER AND THE TEE TO THE GENERATOR AND BETWEEN THE
 TEE FOR THE GENERATOR AND THE TEE AT THE BASE WHERE THE
 PE PIPE SPLITS INTO 2 SECTIONS.WPB AMEND. TO 2010 FBC
 SEC.107.2.1, 107.3.5.3.
 10) THE DESCRIPTION OF WORK ON THE GAS PERMIT
 APPLICATION DOES NOT SHOW THE THREE WATER HEATERS.
 INCLUDE THE THREE HEATERS ON THE SYSTEM AND ADD THE
 ADDITIONAL VALUE ONTO THE THE JOB VALUATION ON THE
 APPLICATION. WPB AMEND. TO 2010 FBC SEC.109.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  