| Plan Review Notes For Permit 15020865 |
| Permit Number |
15020865 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-04-09 16:11:12 | 1) RISER IS CONFLICTING WITH PREVIOUS PERMIT #14100615 | | | FOR KITCHEN AND BATH RENOVATION. PREVIOUS PERMIT | | | INDICATE MAIN HOUSE PANEL IN THE HALLWAY OF MAIN | | | RESIDENCE. REVISE RISER TO INDICATE ALL PANELS AND TO | | | REFLECT ACTUAL FIELD CONDITIONS. | | | 2) LOAD CALCULATION IS CONFLICTING WITH RISER DIAGRAM. | | | LOAD CALCULATION INDICATES A 159AMP TOTAL CONNECTED | | | LOAD. THE RISER DIAGRAM INDICATES A 150AMP ELECTRICAL | | | SERVICE MAIN. REVISE RISER TO INDICATE SERVICE MAIN | | | SIZED TO SUPPORT THE TOTAL CONNECTED LOAD. | | | 3) INDICATE SWITCHED LIGHTS AT THE DOORS OFF OF THE | | | FAMILY ROOM. NEC 210.70(2)(B) | | | 4) INDICATE SMOKE DETECTORS INDIDE AND OUTSIDE OF GUEST | | | ROOM AMD THROUGHOUT MAIN RESIDENCE WHERE REQUIRED. | | | FBC-RESIDENTIAL 314 AND 315. | | | 5) CLARIFY AND REVISE AS NEEDED. PANEL SCHEDULE | | | INDICATES 15AMP CIRCUITS WHERE 20AMP MAY BE REQUIRED. | | | FOR INSTANCE KITCHEN, DINING ROOM AND EXISTING GFI. |
|