| | PROJECT: CHANGE OF OCCUPANCY; BRIDGE CHURCH SCHOOL |
| | PERMIT#: 15020858 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | ELECTRICAL PLANS HAVE NOT BEEN PROVIDED WITH THIS |
| | SUBMITTAL BUT THE MINIMUM CONDITIONS OF THE NEC MUST BE |
| | MET AND INDICATED ON THE PLANS SUBMITTED FOR CODE |
| | COMPLIANCE. PLEASE INDICATE COMPLIANCE WITH THE |
| | FOLLOWING: |
| | |
| | 1) NEC 240.24 (B) OCCUPANCY. |
| | EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL |
| | OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING |
| | THAT OCCUPANCY. INDICATE ON THE PLANS THE LOCATIONS OF |
| | ALL ELECTRICAL PANEL |
| | |
| | 2) NEC 518 ASSEMBLY OCCUPANCY. |
| | WIRING METHODS AND ELECTRICAL SYSTEMS SHALL BE |
| | INSTALLED IN COMPLIANCE WITH THE MINIMUM CONDITIONS |
| | FOUND IN THE NEC ARTICLE 518. |
| | |
| | 3) NEC 422.52 ELECTRIC DRINKING FOUNTAINS. |
| | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH |
| | GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |