| 2015-03-06 15:29:25 | 3/6/2015 |
| | PROJECT: SITE LIGHTING |
| | PERMIT#: 15020847 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| | LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| | ASTRONOMICAL TIME SWITCH. |
| | |
| | 2) 2010 FBC-BUILDING SECTION 1609 |
| | PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES |
| | INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609 |
| | |
| | 3) WPB AMENDMENTS TO FBC 107 |
| | PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE |
| | ELECTRICAL PANELS INTENDED TO BE USED AS THE POWER |
| | SOURCE FOR THE PROPOSED LIGHT POLES. INDICATE THE |
| | EXISTING ELECTRICAL SYSTEM LOAD AND VOLTAGE |
| | |
| | 4) NEC 408.4 |
| | PROVIDE A PANEL SCHEDULE TO INDICATE THE LIGHTING |
| | CIRCUITS PROPOSED TO FEED THE LIGHT POLES. INDICATE ANY |
| | EXISTING CIRCUITS AND THE PROPOSED CIRCUITS FOR THE NEW |
| | LIGHTS. |
| | |
| | 5) NEC 215.5 |
| | PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL PANELS |
| | AND SERVICE PROPOSED TO FEED THE LIGHT POLES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |