Plan Review Notes
Plan Review Notes For Permit 15020842
Permit Number 15020842
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-11 13:53:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ENGINEER (ALI ABOLHASSANI, PE) HAS SIGNED AND SEALED
 A PLAN WITH AN ARCHITECT'S TITLE BLOCK (CUHACI &
 PETERSON). SEE FS 471, 481, FAC61G15-23. RESPONSIBILITY
 FOR THIS SHEET IS NOT CLEAR. DOES THE ENGINEER WORK FOR
 CUHACI & PETERSON? IF THIS IS THE CASE, INCLUDE THE
 ENGINEERING CERTIFICATE OF AUTHORIZATION FOR CUHACI &
 PETERSON. THE CALCS SEALED BY THIS ENGINEER INCLUDES
 ANOTHER COMPANY'S NAME (STRUCTURAL CONCEPTS
 ENGINEERING) IN THE TITLE BLOCK, NOT CUHACI & PETERSON.
  
 2. CALCULATIONS SIGNED AND SEALED BY ALI ABOLHASSANI,
 PE / STRUCTURAL CONCEPTS ENGINEERING LACK THE
 CERTIFICATE OF AUTHORIZATION NUMBER, FS471. THE
 CERTIFICATE OF AUTHORIZATION IS IN DELINQUENT STATUS.
  
 ENGINEER HAS BEEN DISCIPLINED, HAD HIS LICENSE
 SUSPENDED (AND SUBSEQUENTLY REINSTATED) OVER THESE
 ISSUES. PLEASE REVISE PLANS AND CALCS TO BE IN
 COMPLIANCE WITH FS471 AND FAC61G15-23 AND ENSURE THAT
 ALL FUTURE PLANS WILL BE IN COMPLIANCE. IF ENGINEER
 DOES NOT UNDERSTAND THE REQUIREMENTS (LAWS AND RULES),
 PLEASE CONTACT FBPE FOR CLARIFICATION.
  
 3. FBC 2010 BUILDING 1008.1.4.5, SECURITY GRILLS -
 PROVIDE A PLAN WHICH SHOWS COMPLIANCE WITH ALL
 REQUIREMENTS. THE PARTIAL FLOOR PLAN PROVIDED DOES NOT
 SHOW THE EXITS OR REQUIRED NUMBER OF EXITS. COMPLIANCE
 WITH THE OPERATIONAL REQUIREMENTS CAN BE DEMONSTRATED
 IN THE FORM OF A NOTES ON THE PLAN WHICH SHOWS
 COMPLIANCE WITH OTHER REQUIREMENTS.
  