| Plan Review Notes For Permit 15020803 |
| Permit Number |
15020803 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-16 10:40:42 | 1) THE NINTH FLOOR DOES NOT SHOW ANY ACCESSIBLE | | | DRINKING FOUNTAINS WITHIN THE TENANT SPACE OR THE | | | COMMON CORE AREA.COMPLY WITH THE 2010 FAC SEC. 211.2. | | | 2) SUBMIT AN ELEVATION DETAIL FOR THE SINK IN BREAK | | | ROOM # 917 IF THE ROOM IS WITHIN THE SCOPE OF WORK FOR | | | THIS PROJECT. THE SINK SHALL COMPLY WITH THE FAC SEC. | | | 606. | | | 3) THE COFFEE MACHINES AND ANY WATER DISPENSERS SHALL | | | BE PROTECTED AGAINST BACKFLOW PER 2010 FBC | | | SEC.608.16.10.BACKFLOW PREVENTERS SHALL CONFORM TO ASSE | | | 1022. | | | 4) SHT. P1.09 - THE 2" VENT APPEARS TO BE OVER 40 FT. | | | IN DEVELOPED LENGTH THEREFORE THE VENT SHALL BE | | | INCREASED ONE PIPE SIZE FOR THE ENTIRE LENGTH PER THE | | | 2010 FPC SEC.916.2 & 916.4.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|