Plan Review Notes
Plan Review Notes For Permit 15020803
Permit Number 15020803
Review Stop P
Sequence Number 1
Notes
Date Text
2015-03-16 10:40:421) THE NINTH FLOOR DOES NOT SHOW ANY ACCESSIBLE
 DRINKING FOUNTAINS WITHIN THE TENANT SPACE OR THE
 COMMON CORE AREA.COMPLY WITH THE 2010 FAC SEC. 211.2.
 2) SUBMIT AN ELEVATION DETAIL FOR THE SINK IN BREAK
 ROOM # 917 IF THE ROOM IS WITHIN THE SCOPE OF WORK FOR
 THIS PROJECT. THE SINK SHALL COMPLY WITH THE FAC SEC.
 606.
 3) THE COFFEE MACHINES AND ANY WATER DISPENSERS SHALL
 BE PROTECTED AGAINST BACKFLOW PER 2010 FBC
 SEC.608.16.10.BACKFLOW PREVENTERS SHALL CONFORM TO ASSE
 1022.
 4) SHT. P1.09 - THE 2" VENT APPEARS TO BE OVER 40 FT.
 IN DEVELOPED LENGTH THEREFORE THE VENT SHALL BE
 INCREASED ONE PIPE SIZE FOR THE ENTIRE LENGTH PER THE
 2010 FPC SEC.916.2 & 916.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  