| Plan Review Notes For Permit 15020803 |
| Permit Number |
15020803 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-03 13:03:12 | 15020803 | | | 777 S. FLAGLER DR. #1100W | | | PHILLIPS POINT INTERIOR ALTERATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PANEL SCHEDULES DO NOT APPEAR TO MATCH THE ELECTRIC | | | RISER PLAN. PROVIDE A RISER PLAN FOR THE NEW WORK WHICH | | | SHOWS ALL CONDUIT AND WIRE SIZED. SHOW LOCATION AND | | | PROVIDE A MOUNTING DETAIL FOR THE TRANSFORMER. SHOW | | | LOCATION FOR ALL PANELS. NEC 215.5 | | | | | | PROVIDE A FIRE STOP DETAIL FOR ANY WALL OR FLOOR | | | PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21 | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | |
|