2015-03-03 13:03:1215020803
 777 S. FLAGLER DR. #1100W
 PHILLIPS POINT INTERIOR ALTERATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PANEL SCHEDULES DO NOT APPEAR TO MATCH THE ELECTRIC
 RISER PLAN. PROVIDE A RISER PLAN FOR THE NEW WORK WHICH
 SHOWS ALL CONDUIT AND WIRE SIZED. SHOW LOCATION AND
 PROVIDE A MOUNTING DETAIL FOR THE TRANSFORMER. SHOW
 LOCATION FOR ALL PANELS. NEC 215.5
  
 PROVIDE A FIRE STOP DETAIL FOR ANY WALL OR FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
  