Plan Review Notes
Plan Review Notes For Permit 15020719
Permit Number 15020719
Review Stop G
Sequence Number 1
Notes
Date Text
2015-02-27 06:41:071) A PERMIT APPLICATION SHALL BE SUBMITTED FROM A
 LICENSED GAS OR PLUMBING CONTRACTOR FOR THE
 INSTALLATION OF THE GAS PIPING FOR THE NEW POOL HEATER.
 A POOL CONTRACTOR CANNOT INSTALL THE GAS PIPING. WPB
 AMEND. TO 2010 FBC SEC. 105.1, FL. STATUTE 489.
 2) SUBMIT A GAS PIPNG RISER DIAGRAM FOR REVIEW.CLEARLY
 SHOW THE POINT OF DELIVERY, THE LENGTH OF ALL CUT
 SECTIONS OF PIPE, ALL PIPE SIZES. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 3) INDICATE THE TYPE OF PIPE MATERIAL BEING INSTALLED
 FOR THE GAS SYSTEM.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) INDICATE THE BTU LOAD OF THE POOL HEATER ON THE
 PLAN.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 5) SHOW THE DISTANCE FROM THE GAS POINT OF DELIVERY TO
 THE POOL HEATER. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) INDICATE THE GAS DELIVERY PRESSURE. 2010 FBCR
 SEC.G2413.1.
 7) SUBMIT A DETAIL SHOWING THE THE TYPE, SIZE AND
 TERMINATION POINT OF THE GAS VENT IN RELATION TO THE
 STRUCTURE. COMPLY WITH 2010 FBCR SECTIONS G2426, G2427
 8) THE SUBMITTED POOL HEATER SPECIFICATIONS / MANUAL DO
 NOT INDICATE THE MANUFACTURER.SUBMIT SPECIFICATIONS
 THAT CLEARLY SHOW THE MANUFACTURER. 2010 FBCR SEC.
 G2404.3.
 9) SHOW THE LOCATION OF THE POOL HEATER ON THE
 SUBMITTED SURVEY. 2010 WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 10) SHOW THE SIZE OF THE INTAKE & RETURN LINES OF THE
 POOL HEATER ON THE PLANS. 2010 WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 11) SUBMIT 2 COMPLETE COPIES OF THE POOL HEATER
 INSTALLATION MANUAL. ONLY SELECTED PAGES HAVE BEEN
 SUBMITTED. 2010 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 12) INDICATE THE DIMENSIONS (L X W) AND THE THICKNESS
 OF THE EXISTING CONCRETE SLAB.2010 WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 13) INDICATE THE MODEL OF THE POOL HEATER ON THE
 SPECIFICATIONS.2010 WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 14) THE VALUE FOR THIS JOB APPEARS LOW ON THE
 APPLICATION. SUBMIT A DETAILED ESTIMATE OR A SIGNED
 CONTRACT SHOWING THE TOTAL VALUE OF THE JOB PER THE WPB
 AMEND. TO 2010 FBC SEC. 109.3.
 15) THE CITY OF WEST PALM BEACH IS LOCATED IN A 170 MPH
 WIND ZONE.THE MANUF. SPECIFICATIONS SHOW ANCHORING FRO
 A 150 MPH WIND ZONE. SUBMIT ENGINEERING FOR ANCHORING
 OF THE UNIT FOR 170 MPH WINDS OR SUBMIT
 DOCUMENTATION/DETAILS FROM THE MANUFACTURER FOR THE
 WIND LOAD ATTACHMENTS. 2010 FBCR SEC.G2404.6.
 16) PER THE 2010 FBCR SEC. G2404.7, STRUCTURES LOCATED
 IN FLOOD HAZARD AREAS SHALL HAVE THE APPLIANCE,
 EQUIPMENT, AND SYSTEM INSTALLATION REGULATED BY THE
 FLORIDA BUILDING CODE LOCATED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION AND SHALL COMPLY WITH THE FLOOD
 RESISTANT CONSTRUCTION REQUIREMENTS OF 2010 FBCR
 SECTION R322.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  