2015-02-27 09:00:142/27/2015
 PROJECT: POOL HEATER 7441 MONTE VERDE LN
 PERMIT#: 15020719
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WPB AMENDMENTS TO THE FBC 107.3.2
 PROVIDE ELECTRICAL PERMIT APPLICATION AS WELL AS
 ELECTRICAL PLANS AND SPECIFICATIONS TO INDICATE
 COMPLIANCE WITH CODE. INCLUDE THE FOLLOWING:
 THE LOCATION OF THE ELECTRICAL PANEL RELETIVE TO THE
 POOL HEATER. AND A PANEL SCHEDULE. NEC 408.4
 THE DEMOLITION OF THE PREVIOUS ELECTRIC POOL HEATER
 CIRCUIT AND TERMINATION OF PREVIOUS CIRCUITRY. NEC
 110.8
 THE INSTALLATIOON OF THE NEW ELECTRIC IGNIGHTER CIRCUIT
 INCLUDING EQUIPMENT GROUND. NEC 110.8, 250.4, 680.25(B)
 THE INSTALLATION OF THE BOND WIRE TO AN EQUIPOTENTIAL
 GROUND LOOP. NEC 680.26
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  