| | PROJECT: POOL HEATER 7441 MONTE VERDE LN |
| | PERMIT#: 15020719 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) WPB AMENDMENTS TO THE FBC 107.3.2 |
| | PROVIDE ELECTRICAL PERMIT APPLICATION AS WELL AS |
| | ELECTRICAL PLANS AND SPECIFICATIONS TO INDICATE |
| | COMPLIANCE WITH CODE. INCLUDE THE FOLLOWING: |
| | THE LOCATION OF THE ELECTRICAL PANEL RELETIVE TO THE |
| | POOL HEATER. AND A PANEL SCHEDULE. NEC 408.4 |
| | THE DEMOLITION OF THE PREVIOUS ELECTRIC POOL HEATER |
| | CIRCUIT AND TERMINATION OF PREVIOUS CIRCUITRY. NEC |
| | 110.8 |
| | THE INSTALLATIOON OF THE NEW ELECTRIC IGNIGHTER CIRCUIT |
| | INCLUDING EQUIPMENT GROUND. NEC 110.8, 250.4, 680.25(B) |
| | THE INSTALLATION OF THE BOND WIRE TO AN EQUIPOTENTIAL |
| | GROUND LOOP. NEC 680.26 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |