| Plan Review Notes For Permit 15020691 |
| Permit Number |
15020691 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-25 05:50:04 | THERE WAS NO GAS DRAWING SHOWN ON THE ORIGINAL PLAN. | | | 1) THE ORIGINAL FLOOR PLAN SHOWED THE GAS FIREPLACE TO | | | BE REMOVED AND THE GAS DRAWING SHOWS THE FIREPLACE TO | | | REMAIN. CLARIFY. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS SHEETS & | | | INSTALLATION INSTRUCTIONS FOR ALL GAS APPLIANCES. | | | APPLIANCES SHALL BE LISTED AND LABELED PER THE 2010 | | | FUEL GAS CODE SEC. 301.3. | | | 3) SIZE THE PIPE DROPS TO THE GAS RANGE AND THE | | | FIREPLACE AND INDICATE THE TYPE OF PIPE FOR BOTH DROPS. | | | 40 SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL | | | APPLIANCES IN ACCORDANCE WITH THE 2010 FUEL GAS CODE | | | SEC.304. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|