| Plan Review Notes For Permit 15020685 |
| Permit Number |
15020685 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-04-07 14:06:52 | 1) THE SITE PLAN SHALL BE SIGNED & SEALED BY THE DESIGN | | | PROFESSIONAL OF RECORD PER THE F.A.C. SEC. 61G1-16.003. | | | 2) THE SITE PLAN SHOWS A NOTE THAT SAYS "EXISTING | | | BACKFLOW PREVENTER"AND AN ARROW POINTING TO NOWHERE. | | | CLARIFY THE LOCATION OF THE DEVICE ON THE PLAN AND | | | INDICATE HOW THE 3/4 WATER SERVICE IS CONNECTED TO THE | | | EXISTING BUILDING. WHAT IS IT TYING INTO? | | | 3) THE WATER SERVICE TO THE TRAILER IS TO BE BURIED | | | WITH A MIN. OF 12" OF COVER. I AM ASSUMING THIS WILL BE | | | DONE BUT IT IS UNCLEAR ON THE DRAWING HOW THIS PIPING | | | WILL BE INSTALLED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|