| Plan Review Notes For Permit 15020678 |
| Permit Number |
15020678 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-12 11:36:13 | 1) SHT. DET-2 , DETAIL # 3 - THE REQUIRED KNEE | | | CLEARANCCE SHALL BE 11 INCHES DEEP MINIMUM AT 9 INCHES | | | ABOVE THE FINISH FLOOR OR GROUND AND 8 INCHES DEEP | | | MINIMUM AT 27 INCHES ABOVE THE FINISH FLOOR OR GROUND. | | | FAC SEC.306.3.3. | | | 2) SHT. DET - 2, DETAIL #2 - FIGURE 608.2.1. - THE 36" | | | X 48" CLEAR FLOOR SPACE AT THE SHOWER ENTRANCE IS | | | MISALIGNED. THE CLEAR FLOOR SPACE SHALL BEGIN AT THE | | | INSIDE OF THE CONTROL WALL. THE PLAN SHOWS THE CLEAR | | | FLOOR SPACE STARTING LINE IN THE CENTER OF THE WALL. | | | 3) SHT. DET-2 - SOME OF HE NUMBERS FOR THE ACCCESSIBLE | | | FIGURES DO NOT MATCH THE FIGURE NUMBERS THAT ARE LISTED | | | IN THE FL. ACCESSIBILITY CODE IF YOUR INTENT WAS TO | | | MATCH THOSE DETAILS. CLARIFY. | | | 4) SHT. P6.31A - THERE IS NO WATER OR SANITARY RISER | | | FOR ROOMS T3200 , T3283 & T3284. CLARIFY. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|