Text |
| 2015-03-11 13:05:02 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15020678 |
| | ADD: 1309 N FLAGLER DR. |
| | CONT: WESTBROOKE |
| | TEL: (561)395-4126 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 1) SHEET EP-O DETAIL # 4 SEE SINGLE LINE AT PARKING |
| | STALL NOT CITY STANDARD. NOTE DET-1/ DETAIL 7 IS NOT |
| | CITY STANDARD EITHER, SEE W. P. B. MUNI CODE 94-485 FOR |
| | DOUBLE STRIPE. |
| | |
| | 2) SHEET EP-1: |
| | 2A) DETAIL # 5 DOESN'T INDICATE THE CHANGE TO BE MADE. |
| | DOOR TO ROOM 473A DOES NOT HAVE THE REQUIRED 18" ON THE |
| | LATCH SIDE OF DOOR. FBC-ACC. CODE 404.2.4. |
| | |
| | 2B) DETAIL # 10 DOESN'T INDICATE THE CHANGE TO BE MADE. |
| | SEE ROOM 3146 DOORS IN SERIES. FL ACC. CODE 404.2.6. |
| | |
| | 3) SHEET EP-3: |
| | 3A) DETAIL # 2 NEW ACCESSIBLE BENCH LOCATION. SEE DET 4 |
| | DETAIL 11 THE DETAIL IS NOT CLEAR THE BENCH IS ATTACHED |
| | TO THE WALL( NUMBER OF FASTENERS NOR SIZE) NOR DOES IT |
| | INDICATE A BACK SUPPORT. FL ACC. CODE 903.4. |
| | |
| | 3B) DETAIL # 3 DOES NOT SHOW ANY CHANGE. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3C) DETAIL # 6 NO CHANGE. MENS TOILET ROOM TB044 AT |
| | ENTRY DOOR MISSING THE 18 INCHES LATCH SIDE OF DOOR. FL |
| | ACC. CODE 404.2.4 MANEUVERING CLEARANCES. |
| | |
| | 4)SHEET DET-2 SEE FIGURE 608.2.1 36X36 INCH SHOWER, THE |
| | 48 INCHES IS TO BE TAKEN FROM THE FACE OF THE CONTROL |
| | WALL. FL ACC. CODE FIGURE 608.2.1. |
| | |
| | 5) SHEET DET-4: |
| | 5A) DETAIL # 3 TYPICAL DUCT PENETRATION SHOW EITHER UL |
| | LISTING OR GYPSUM LISTING FOR PENETRATION THROUGH FIRE |
| | RATED WALLS. 713.1.1 DUCTS AND AIR TRANSFER OPENINGS. |
| | PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS |
| | THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH |
| | SECTIONS 713.2 THROUGH 713.3.3. PENETRATIONS OF |
| | HORIZONTAL ASSEMBLIES NOT PROTECTED WITH A SHAFT AS |
| | PERMITTED BY EXCEPTION 4 OF SECTION 708.2, AND NOT |
| | REQUIRED TO BE PROTECTED WITH FIRE DAMPERS BY OTHER |
| | SECTIONS OF THIS CODE, SHALL COMPLY WITH SECTIONS 713.4 |
| | THROUGH 713.4.2.2. DUCTS AND AIR TRANSFER OPENINGS THAT |
| | ARE PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTION |
| | 716. |
| | |
| | 5B) DETAIL # 4 SHOWS IN PRINT THIS IS A MASONRY WALL |
| | SECTION, WHERE AS IN VIEWING THE SECTION IT IS SOLID AS |
| | A POURED CONCRETE WALL WOULD BE. PLEASE PROVIDE CODE |
| | COMPLIANCE WITH : |
| | FBC-B 713.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. |
| | |
| | FBC-B 713.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. |
| | THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| | ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| | THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| | PENETRATED. |
| | |
| | 5C) DETAIL # 8 SHOWS A FIRE EXTINGUISHER BOX WITH THE |
| | BACK WALL ONLY ONE LAYER OF DRYWALL PLEASE PROVIDE |
| | COMPLIANCE WITH FBC-B 713.3.2 MEMBRANE PENETRATIONS. |
| | MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION |
| | 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE |
| | A FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE |
| | INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL |
| | NOT BE REDUCED. IF AN APPROVED FIRE STOP SYSTEM IS |
| | PROVIDED PLEASE PROVIDE THE ASSEMBLY. |
| | |
| | 5D) DETAIL # 12 THE RECEPTION DESKDOES NOT PROVIDE THE |
| | LENGTH OF THE ACCESSIBLE PORTION OF THE UNIT. SHOW |
| | COMPLIANCE FOR : |
| | 2010 FBC- ACC. CODE 904.4.1 PARELLEL APPROACH AND |
| | 904.4.2 FORWARD APPROACH. |
| | |
| | 6) SHEET A7.0 DETAILS 1 & 2 BOTH INDICATE A U L LISTING |
| | OR EQUAL TO. PLEASE REVIEW 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561) 805-6715 |
| | FAX: (561)805-6676 |
| | E-MAIL: [email protected] |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |