Plan Review Notes
Plan Review Notes For Permit 15020676
Permit Number 15020676
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-08 08:49:01NO ELECTRICAL PLAN HAS BEEN INCLUDED IN THE SUBMITTAL
 PACKAGE. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT
 THIS TIME. AN ELECTRICAL PERMIT IS REQUIRED FOR AN
 ELECTRICAL CONTRACTOR TO COMPLETE THE ELECTRICAL
 CONNECTION REQUIRED FOR THE IGNITER IN A GAS TANKLESS
 WATER HEATER.
  
 1) PROVIDE AN ELECTRICAL PERMIT APPLICATION WITH A
 FLOOR PLAN AND A PANEL SCHEDULE INDICATING THE
 ELECTRICAL CIRCUIT AND DISCONNECT REQUIRED FOR THE NEW
 GAS TANKLESS WATER HEATER. NEC 422.31
  
 2) PROVIDE ADDITIONAL INFORMATION ON THE FLOOR PLAN AND
 PANEL SCHEDULE THAT INDICATE THE DEMOLITION OF THE
 ASSUMED PREVIOUSLY EXISTING STORAGE WATER HEATER. WPB
 AMENDMENTS TO THE FBC 107.3.2
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]