| Notes |
| Date |
Text |
| 2015-03-21 06:19:45 | 1) INDICATE ON THE PLAN THE TYPE OF PIPE BEING | | | INSTALLED FOR THE GAS SYSTEM. THE RESPONSE FROM THE | | | ENGINEER REFERS TO PLUMBING SHT. P0.2 BUT THERE IS NO | | | SUCH DRAWING IN THE SET OF SUBMITTED PLANS. CLARIFY. | | | 2) INDICATE THE DELIVERY PRESSURE OF THE GAS PER THE | | | 2010 FBC FUEL GAS CODE SEC.402.2. THE RESPONSE FROM THE | | | ENGINEER REFERS TO PLUMBING SHT. P0.2 BUT THERE IS NO | | | SUCH DRAWING IN THE SET OF SUBMITTED PLANS. CLARIFY. | | | 3) SUBMIT REFERENCED DRAWING P0.2 FOR REVIEW. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|