| Plan Review Notes For Permit 15020647 |
| Permit Number |
15020647 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-23 16:05:04 | 3/23/2015 | | | PROJECT: SUSHIYAMA SIGN | | | PERMIT#: 15020647 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION | | | | | | 1) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING | | | ? FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND | | | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS | | | OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3 | | | LISTING. | | | | | | 2) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE | | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC | | | 600.6(A)(1) | | | | | | 3) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 | | | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT | | | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & | | | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME | | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING | | | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E | | | 505.2.4 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|