| Plan Review Notes For Permit 15020619 |
| Permit Number |
15020619 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-04-06 10:27:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS LIST: | | | | | | 1. 7/8" EDGE DISTANCE IS NOT ADEQUATE FOR CONCRETE OR | | | MASONRY SUBSTRATE, SEE PAGE 7. FBC 2010 RESIDENTIAL | | | 301. | | | | | | 2ND REVIEW, THIS HAS BEEN CHANGED TO 1". PLEASE SEE THE | | | ANCHOR CHART WHICH YOU HIGHLIGHTED ON SHEET 7. THIS IS | | | NOT ADEQUATE FOR THE FASTENER SELECTED. | | | | | | NEW COMMENTS: | | | | | | TWO DIFFERENT FASTENERS HIGHLIGHTED ON THE PRODUCT | | | APPROVAL, BUT ONLY ONE SPECIFIED IN THE INSTALLATION | | | SCHEDULE. CLARIFY. | | | | | | ONLY ONE SET OF THE INSTALLATION SCHEDULE WAS PROVIDED. | | | TWO COMPLETE COLLATED SETS OF PLANS REQUIRED FOR PERMIT | | | ISSUANCE. THERE IS A COPY FACILITY LOCATED WITHIN | | | WALKING DISTANCE OF THE BUILDING DIVISION. THE LIBARARY | | | WILL ALLOW FOR YOU TO PRINT DOCUMENTS FROM THE | | | INTERNET. PLEASE MAKE PROVISIONS FOR TWO COMPLETE SETS | | | OF DOCUMENTS PRIOR TO SUBMITTAL TO THIS DEPARTMENT. DUE | | | TO WORK LOAD, WE ARE NOT ALWAYS ABLE TO PROVIDE | | | PHOTOCOPY SERVICES. IF ONLY ONE SET IS PROVIDED, AN | | | ADMINISTRATIVE FEE AND PHOTOCOPY FEE WILL BE ASSESSED. | | | | | | PROVIDE A ROOM DESIGNATION FOR THE EMERGENCY MEANS OF | | | ESCAPE, FBC 2010 RESIDENTIAL 310.4. | | | | | | | | | | | | | | | |
|