| 2015-02-18 14:58:25 | 2/18/2015 |
| | PROJECT: KITCHEN REMODEL |
| | PERMIT#: 15020583 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE PLANS TO ADDRESS REVIEW COMMENTS LISTED BELOW: |
| | |
| | 1) PROVIDE ORIGINAL KITCHEN LAYOUT TO DETERMINE ANY |
| | VARIANCE IN DESIGN LAYOUT FROM OLD TO NEW. |
| | |
| | 2) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN |
| | CORRESPONDING TO THE PANEL SCHEDULE. |
| | |
| | 3) PROVIDE LOCATION OF THE ELECTRICAL PANEL. PROVIDE |
| | THE PANEL SCHEDULE, TO INCLUDE CIRCUIT SIZE, 1POLE OR |
| | TWO POLE, AMPERARE OF OCPD AND CORRESPONDING WIRE SIZE. |
| | |
| | 4) INDICATE NEW CIRCUITS AND EXISTING TO REMAIN. |
| | |
| | 5) PROVIDE VERIFICATION FOR THE REQUIREMENT OF |
| | INTERCONNECTED SMOKE AND CARBON MONOXIDE DETECTORS. IF |
| | THEY ARE NOT EXISTING MUST BE INSTALLED. IF THEY MUST |
| | BE INSTALLED THE LOCATIONS NEED TO BE IDENTIFIED ON THE |
| | FLOOR PLAN. FBC-R 314, 315 |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR DAHAYES@WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |