2015-05-29 07:42:03MECHANICAL APPROVED WITH EXCEPTION.
 REVISION REQUIRED FOR MISSING FIRE DAMPERS AT THE
 FOLLOWING LOCATIONS:
 1) SHEET M1.5- EXHAUST DUCT PENETRATING
 CORRIDOR/HISTOLOGY WALL (SEE NOTE 22)
 2) M1.6- EXHAUST INLET AT BREAKROOM/JANITOR CLOSET WALL
 (SEE NOTE 5)
 3) M1.7- THE TWO RATED ENCLOSURES AT LAB STORAGE SHOW
 DAMPERS ON ONLY ONE SIDE OF EACH ENCLOSURE. DAMPERS
 REQUIRED ON ALL FOUR WALLS BEING PENETRATED.
  
 PRODUCT DATA SHEETS TO BE ONSITE FOR FIRE DAMPERS,
 FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTORS, AHU'S, REHEAT
 COILS, EXHAUST FANS, HEAT EXHANGE COMPONENTS, CHILLER
 PIPING AND VALVES, HYDRONIC PUMPS, AIR SCRUBBERS AND
 HEPA FILTERS.
 SMOKE TEST, AND TEST AND BALANCE REPORT REQUIRED FOR
 FINAL APPROVAL.
  