Plan Review Notes
Plan Review Notes For Permit 15020567
Permit Number 15020567
Review Stop B
Sequence Number 2
Notes
Date Text
2015-05-26 10:30:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020567
 ADD: 901 45TH ST ST. MARYS HOSPITAL
 CONT: WESTBROOKE
 TEL: (561)395-4126
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MAY 26/2015
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A1.0 OFFICE CL 107 HAD THE 2 DOORS IN SERIES,
 THE NEW DESIGN NOW HAS THE DOOR THAT LEADS INTO THE
 CORRIDOR IS NOW IN CONFLICT WITH DOOR # CL105A 21.02N.
 THE OFFICE DOOR CL 107 AT THE CORRIDOR DOES NOT HAVE
 THE REQUIRED 60 INCHES CLEAR FLOOR SPACE AS REQUIRED BY
 THE 2010 FBC-ACCESSIBILITY SEE FIGURE 404.2.4.1(A). THE
 DOUBLE ACTING DOOR ON THE FAR SIDE OF THE CORRIDOR WILL
 HIT A WHEELCHAIR WITH THIS TYPE OF CONFIGURATION.
  
 2) SHEET A2.0. THE CUSTOM CURB FOR THE EXHAUST FANS AND
 AIR HANDLER UNITS WILL REQUIRE THE ENGINEERED SHOP
 DRAWINGS AND CALCULATIONS AS WELL AS THE ATTACHMENT
 FROM THE EXHAUST FAN & AIR HANDLER UNIT, AND THE CUSTOM
 CURB TO THE STRUCTURAL ROOF SYSTEM. THE DELEGATE
 ENGINEERS DESIGN MUST 1ST BE SUBMITTED TO THE ENGINEER
 OF RECORD FOR REVIEW AN APPROVAL BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 2010 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 2010 FBC-B 1609.8 ROOFTOP STRUCTURES & EQUIPMENT.
 2010 FBC-M 301.12 WIND RESISTANCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  