| 2015-05-26 10:30:19 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15020567 |
| | ADD: 901 45TH ST ST. MARYS HOSPITAL |
| | CONT: WESTBROOKE |
| | TEL: (561)395-4126 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. MAY 26/2015 |
| | ACTION: BUILDING PROVISO |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET A1.0 OFFICE CL 107 HAD THE 2 DOORS IN SERIES, |
| | THE NEW DESIGN NOW HAS THE DOOR THAT LEADS INTO THE |
| | CORRIDOR IS NOW IN CONFLICT WITH DOOR # CL105A 21.02N. |
| | THE OFFICE DOOR CL 107 AT THE CORRIDOR DOES NOT HAVE |
| | THE REQUIRED 60 INCHES CLEAR FLOOR SPACE AS REQUIRED BY |
| | THE 2010 FBC-ACCESSIBILITY SEE FIGURE 404.2.4.1(A). THE |
| | DOUBLE ACTING DOOR ON THE FAR SIDE OF THE CORRIDOR WILL |
| | HIT A WHEELCHAIR WITH THIS TYPE OF CONFIGURATION. |
| | |
| | 2) SHEET A2.0. THE CUSTOM CURB FOR THE EXHAUST FANS AND |
| | AIR HANDLER UNITS WILL REQUIRE THE ENGINEERED SHOP |
| | DRAWINGS AND CALCULATIONS AS WELL AS THE ATTACHMENT |
| | FROM THE EXHAUST FAN & AIR HANDLER UNIT, AND THE CUSTOM |
| | CURB TO THE STRUCTURAL ROOF SYSTEM. THE DELEGATE |
| | ENGINEERS DESIGN MUST 1ST BE SUBMITTED TO THE ENGINEER |
| | OF RECORD FOR REVIEW AN APPROVAL BEFORE SUBMISSION TO |
| | THE BUILDING DEPARTMENT. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 2010 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | 2010 FBC-B 1609.8 ROOFTOP STRUCTURES & EQUIPMENT. |
| | 2010 FBC-M 301.12 WIND RESISTANCE. |
| | |