| Plan Review Notes For Permit 15020567 |
| Permit Number |
15020567 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-20 09:36:30 | PLAN DENIED | | | 1) MISSING 3 FIRE DAMPERS ON EXHAUST FAN 103 | | | 16 X 8 DUCT AND 8 X 8 DUCT. PAGE M1.7 SHOWS | | | A 2 HR WALL AND PAGE M1.6 SHOWS NO RATING | | | AT ALL. PLEASE CLARIFY. SECTION 607.5.2 FIRE | | | BARRIERS 2010 FBC (M) | | | 2) EXHAUST DUST IN BLOOD BANK ROOM PAGE | | | M1.7 8 X 8 DUCT WHERE IS THE DUCT GOING AND | | | WHAT EXHAUST FAN IS IT GOING TO. 107 FBC 2010 | | | 3) WALK IN COOLERS REQUIRE SEPARATE APPLICATION | | | PLAN AND PERMIT. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 567-805-6676 |
|