Plan Review Notes
Plan Review Notes For Permit 15020567
Permit Number 15020567
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-05 12:01:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020567
 ADD: 901 45TH ST ST. MARYS HOSPITAL
 CONT: WESTBROOKE
 TEL: (561)395-4126
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS. MARCH 5/2015
 ACTION: DENIED
  
 1) SHEET A1.0 OFFICE CL 107 HAS (2) DOORS IN SERIES,
 CL107 & CL107A WITH LESS THAN 4 FT IN BETWEEN. PLEASE
 REVIEW 2010 FBC ACCESS. CODE 404.2.6 DOORS IN SERIES .
 THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM)
 MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO
 THE SPACE.
  
 2) SHEET S-1 NOTE FOR ALL ROOF TOP UNITS INDICATES ALL
 RTUS TO BE SUPPORTED BY A 36 INCH HIGH CURB. NO PRODUCT
 APPROVALS WERE SUBMITTED FOR ROOF TOP CURBS. NOTE IF NO
 PRODUCT APPROVALS CAN BE FOUND FOR A 36 INCH HIGH CURB
 THEN THEY WILL NEED TO BE ENGINEERED SYSTEM. NOTE THIS
 IS A RISK CATEGORY III BUILDING. 1609.8 ROOFTOP
 STRUCTURES AND EQUIPMENT.
  
 3) SHEET S1 AND S2 SHOW NEW EXHAUST FANS AND ROOF
 CURBING, NONE OF THE STRUCTURAL SHEETS PROVIDE THE VASD
 PRESSURES NOR THE ROOF ZONE LOCATIONS 1,2 OR 3 ROOF
 ZONES. THIS IS NEEDED TO EVALUATE THE PRODUCT APPROVALS
 FOR CODE COMPLIANCE FOR PRESSURES. FBC-B1609.
 COMPONENTS AND CLADDING SECTION.
  
 4) MISSING ROOF CURBS FOR EXHAUST FANS, 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS
 & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 5) THE SUBMITTED ROOFING NOA 13-0529.07 JOHN MANVILLE
 BUILT -UP ROOF SYSTEMS OVER CONCRETE DECK. PLEASE
 IDENTIY WHICH SUB-SYSTEM IS TO BE INSTALLED AND
 ASSOCIATED PRESSURES. PLEASE NOTE IF LIMITATION # 7,
 ENHANCED FASTENING BY A FL. ENGINEER IS REQUIRED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]