| 2015-05-05 13:49:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. DUE TO THE EXTENT OF THE PROPOSED WORK AS WELL AS | | | THE POSSIBLE EFFECT ON ADJACENT PROPERTIES, PROVIDE | | | ENGINEERING. NOTE THAT THE RETAINING WALL BLOCK SPEC | | | SHEETS STATE THAT AN UNREINFORCED APPLICATION WILL | | | REQUIRE REVIEW BY A LOCAL PROFESSIONAL ENGINEER, FBC | | | 1601. | | | | | | ENGINEERING IS TO ADDRESS POTENTIAL DRAINAGE ISSUES. NO | | | INFORMATION WAS PROVIDED REGARDING SPOT ELEVATIONS, | | | EXISTING GRADES, ETC. CONSTRUCTION CANNOT HAVE A | | | DETRIMENTAL EFFECT ON ADJACENT PROPERTIES OR THE RIGHT | | | OF WAY, FBC 110.7. | | | | | | |
|