Plan Review Notes
Plan Review Notes For Permit 15020561
Permit Number 15020561
Review Stop B
Sequence Number 2
Notes
Date Text
2015-05-05 13:49:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DUE TO THE EXTENT OF THE PROPOSED WORK AS WELL AS
 THE POSSIBLE EFFECT ON ADJACENT PROPERTIES, PROVIDE
 ENGINEERING. NOTE THAT THE RETAINING WALL BLOCK SPEC
 SHEETS STATE THAT AN UNREINFORCED APPLICATION WILL
 REQUIRE REVIEW BY A LOCAL PROFESSIONAL ENGINEER, FBC
 1601.
  
 ENGINEERING IS TO ADDRESS POTENTIAL DRAINAGE ISSUES. NO
 INFORMATION WAS PROVIDED REGARDING SPOT ELEVATIONS,
 EXISTING GRADES, ETC. CONSTRUCTION CANNOT HAVE A
 DETRIMENTAL EFFECT ON ADJACENT PROPERTIES OR THE RIGHT
 OF WAY, FBC 110.7.
  
  