| 2015-06-25 15:33:00 | 6/25/2015 |
| | PROJECT: SPRINGDALE |
| | PERMIT#: 15020549 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) NEC 215.2 MINIMUM RATING AND SIZE. |
| | PROVIDE A LOAD CALCULATION IN ACCORDANCE WITH THE |
| | PROVISIONS OF THE THE NEC 220.16. 215.2 MINIMUM RATING |
| | AND SIZE AND REVISE THE RISER DIAGRAM AS NEEDED . |
| | (A) FEEDERS NOT MORE THAN 600 VOLTS. (1) GENERAL. |
| | FEEDER CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN |
| | REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN PARTS III, |
| | IV, AND V OF ARTICLE 220. |
| | |
| | 2) REVISE THE RISER DIAGRAM. THE CURRENT DESIGN IS |
| | INDICATING FEEDER CONDUCTORS UTILIZING A SERVICE |
| | DISCONNECT AS A RACEWAY. |
| | 2A) REVISE THE GROUNDING ELECTRODE SYSTEM IN THE RISER |
| | DIAGRAM. THE CURRENT DESIGN INDICATES THE GROUNDING |
| | ELECTRODE CONDUTOR TERMINATING AT ONLY ONE OF THE TWO |
| | MAIN DISCONNECTS. |
| | |
| | 3) NEC 110.33(B) |
| | PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| | GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| | EQUIPMENT INSTALLED IN THE ATTIC FOR THE AHU(S). NEC |
| | 110.33(B) |
| | |
| | 4) FBC-E 402.4.5 RECESSED LIGHTING. |
| | RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED |
| | LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING |
| | ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE |
| | DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF |
| | AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING |
| | CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A |
| | GASKET OR CAULK BETWEEN THE HOUSING AND THE INTERIOR |
| | WALL OR CEILING COVERING. |
| | |
| | 5) FBC-E 404.1 LIGHTING EQUIPMENT. |
| | A MINIMUM OF 50 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICENCY |
| | LAMPS. |
| | |
| | 6) NEC210.8 |
| | CLARIFY ALL OUTLTS REQUIRING GFI PROTECTION. SEVERAL |
| | LOCATIONS NOT INDICATING PROPER GFI PROTECTION. GARAGE |
| | DOOR OUTLETS , KITCHEN COUNTER OUTLETS, BACK LANIA |
| | OUTLETS. SEE NEC210.8 |
| | |
| | 7) NEC 210.12, 406.11 |
| | ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SWIMMING POOLS, GENERATORS. LOW |
| | VOLTAGE SYSTEMS, SECURITY, CABLE TV,, CCTV, |
| | AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |