| Date |
Text |
| 2015-03-28 14:27:02 | 3/28/2015 |
| | PROJECT: SPRINGDALE |
| | PERMIT#: 15020549 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NEC 215.2 MINIMUM RATING AND SIZE. |
| | PROVIDE A LOAD CALCULATION IN ACCORDANCE WITH THE |
| | PROVISIONS OF THE THE NEC 220.16. 215.2 MINIMUM RATING |
| | AND SIZE AND REVISE THE RISER DIAGRAM AS NEEDED . |
| | (A) FEEDERS NOT MORE THAN 600 VOLTS. (1) GENERAL. |
| | FEEDER CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN |
| | REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN PARTS III, |
| | IV, AND V OF ARTICLE 220. |
| | |
| | 2) NEC 440.11 |
| | REVISE THE SYMBOL SHOWN FOR THE AHU 1 IN THE ATTIC |
| | SPACE IN THE GARAGE AND FOR THE CU UNIT(S) OUTSIDE. THE |
| | SYMBOL INDICATES A 240V RECEPTACLE OUTLET WHERE AN A/C |
| | UNITS REQUIRE DISCONNECTING MEANS CAPABLE OF |
| | DISCONNECTING THE UNITS FROM THE CIRCUIT CONDUCTORS. |
| | NEC 440.11 |
| | |
| | 3) NEC 110.33(B) |
| | PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| | GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| | EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| | MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| | NEC 110.33(B) |
| | |
| | 4) FBC-E 402.4.5 RECESSED LIGHTING. |
| | RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED |
| | LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING |
| | ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE |
| | DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF |
| | AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING |
| | CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A |
| | GASKET OR CAULK BETWEEN THE HOUSING AND THE INTERIOR |
| | WALL OR CEILING COVERING. |
| | |
| | 5) FBC-E 404.1 LIGHTING EQUIPMENT. |
| | A MINIMUM OF 50 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS. |
| | |
| | 6) FBC-R 315.1 CARBON MONOXIDE PROTECTION. |
| | PROVIDE CARBON MONOXIDE DETECTOS WITHIN 10FT. OF |
| | SLEEPING AREAS. |
| | |
| | 7) NEC210.8 |
| | CLARIFY ALL OUTLTS REQUIRING GFI PROTECTION. SEVERAL |
| | LOCATIONS NOT INDICATING PROPER GFI PROTECTION. SEE |
| | NEC210.8 |
| | |
| | 8) NEC 210.12, 406.11 |
| | ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SWIMMING POOLS, GENERATORS. LOW |
| | VOLTAGE SYSTEMS, SECURITY, CABLE TV,, CCTV, |
| | AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |