| Plan Review Notes For Permit 15020522 |
| Permit Number |
15020522 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-02-25 17:17:55 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | REPEAT COMMENT. THE RAS 117 CALCULATIONS SPECIFY THAT | | | THE EXPOSURE CATEGORY IS C, WHEN IT SHOULD BE D. SEE | | | PREVIOUS COMMENT BELOW. | | | 1) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE | | | INTERCOASTAL WATERWAY AND IS THEREFORE CONSIDERED | | | EXPOSURE CATEGORY "D". THE MAXIMUM DESIGN PRESSURE FOR | | | THE ROOFING SYSTEM THAT YOU SUBMITTED IS -45 PSF, WHICH | | | IS NOT ENOUGH TO RESIST THE REQUIRED WIND LOADS. SUBMIT | | | TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7 | | | ON PAGE 16 OF NOA NO. 13-1022.15 | | | |
|