| Date |
Text |
| 2015-09-15 18:43:42 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. THE FBC IN EFFECT IS THE 5TH EDITION 2014 NOT THE |
| | 2010. |
| | 2. PER NEC 406.9(B), ALL OUTDOOR 15 ? 20 AMP |
| | NON-LOCKING RECEPTACLES SHALL BE LISTED |
| | WEATHER-RESISTANT TYPE ?WR?. |
| | 3. LOADS AS REFLECTED ON SHEET E.1 FOR PANELS A, B & D |
| | DO NOT MATCH THE CALCS EXPRESSED ON SHEET E.0. |
| | 4. THE FIRE STOPPING NOTES AS EXPRESSED ON THE PLANS |
| | ONLY APPLY WHEN USING A NON-COMMUNICATING PARTITION, |
| | OTHERWISE ALL ELECTRICAL BOXES IN A RATED WALL SHALL BE |
| | PROPERLY FIRE STOPPED. |
| | 5. THE SMOKE DETECTOR PLACEMENT NOTES SHALL ALSO |
| | INCLUDE ?36 INCHES AWAY FROM THE TIP OF A CEILING FAN |
| | BLADE, OR THE DOOR TO A BATHROOM HOUSING A SHOWER OR |
| | TUB?. |
| | 6. PANEL ?E? APPEARS TO HAVE A CONNECTED LOAD GREATER |
| | THAN THE BUS RATING INDICATED. |
| | 7. CLARIFY THE GENERATOR SIZE. THE PLANS CALL FOR A 25 |
| | KW, AND THE SUBMITTED SPEC SHEET IS FOR A 22 OR 27 KW |
| | UNIT. PROVIDE THE PROPER SPEC SHEET FOR THE APPLICABLE |
| | GENERATOR AND IF THE SHEET IS MORE MULTIPLE UNITS |
| | MARK/HIGHLIGHT THE PROPOSED/INTENDED UNIT. |
| | 8. THE CALCS FOR THE MDP FAIL TO INCLUDE THE LOADS TO |
| | PANEL ?E?. |
| | 9. THE CONNECTED LOAD AT THE MDP EXCEEDS THE MCB RATING |
| | INDICATED. |
| | 10. THE LOADS FOR THE MDP OF SHEET E.0 DO NOT MATCH |
| | THOSE OF SHEET E.1 |
| | 11. NEC 210.70(A)(3), REQUIRES THAT THERE BE A LIGHT IN |
| | THE CLOSET WHERE THE SMART BOX IS LOCATED. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |