Plan Review Notes
Plan Review Notes For Permit 15020495
Permit Number 15020495
Review Stop E
Sequence Number 3
Notes
Date Text
2015-09-15 18:43:42PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE FBC IN EFFECT IS THE 5TH EDITION 2014 NOT THE
 2010.
 2. PER NEC 406.9(B), ALL OUTDOOR 15 ? 20 AMP
 NON-LOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE ?WR?.
 3. LOADS AS REFLECTED ON SHEET E.1 FOR PANELS A, B & D
 DO NOT MATCH THE CALCS EXPRESSED ON SHEET E.0.
 4. THE FIRE STOPPING NOTES AS EXPRESSED ON THE PLANS
 ONLY APPLY WHEN USING A NON-COMMUNICATING PARTITION,
 OTHERWISE ALL ELECTRICAL BOXES IN A RATED WALL SHALL BE
 PROPERLY FIRE STOPPED.
 5. THE SMOKE DETECTOR PLACEMENT NOTES SHALL ALSO
 INCLUDE ?36 INCHES AWAY FROM THE TIP OF A CEILING FAN
 BLADE, OR THE DOOR TO A BATHROOM HOUSING A SHOWER OR
 TUB?.
 6. PANEL ?E? APPEARS TO HAVE A CONNECTED LOAD GREATER
 THAN THE BUS RATING INDICATED.
 7. CLARIFY THE GENERATOR SIZE. THE PLANS CALL FOR A 25
 KW, AND THE SUBMITTED SPEC SHEET IS FOR A 22 OR 27 KW
 UNIT. PROVIDE THE PROPER SPEC SHEET FOR THE APPLICABLE
 GENERATOR AND IF THE SHEET IS MORE MULTIPLE UNITS
 MARK/HIGHLIGHT THE PROPOSED/INTENDED UNIT.
 8. THE CALCS FOR THE MDP FAIL TO INCLUDE THE LOADS TO
 PANEL ?E?.
 9. THE CONNECTED LOAD AT THE MDP EXCEEDS THE MCB RATING
 INDICATED.
 10. THE LOADS FOR THE MDP OF SHEET E.0 DO NOT MATCH
 THOSE OF SHEET E.1
 11. NEC 210.70(A)(3), REQUIRES THAT THERE BE A LIGHT IN
 THE CLOSET WHERE THE SMART BOX IS LOCATED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  