| 2015-09-04 17:46:54 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ACCORDING THE DRAWING INDEX ON SHEET A-0.2, THERE |
| | APPEARS TO BE SOME SHEETS MISSING FROM THE PLANS. |
| | SHEETS S-10, SP-1.3 AND A-6.4 ARE NOT IN THE PLANS. FBC |
| | 107.2.1 |
| | |
| | 2) THERE ARE SHEETS IN THE PLANS THAT ARE NOT LISTED IN |
| | THE DRAWING INDEX. SHEETS A-8.3, S0 AND S12 ARE NOT |
| | LISTED. FBC 107.2.1 |
| | |
| | 3) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| | EFFICIENCY FORMS. FBC ENERGY SECTION 405. |
| | |
| | 4) REVISE THE PRODUCT APPROVAL NUMBERS IN THE EXTERIOR |
| | DOOR SCHEDULE ON SHEET A3.1 AND SUBMIT THE CORRECT |
| | CURRENT ONES. NOA NO. 14-0123.10 AND NOA NO.14-1117.05 |
| | ARE EXPIRED. NOA NO. 12-1231.06 IS FOR FRENCH DOORS AND |
| | PLANS SPECIFY SLIDING GLASS DOORS. |
| | |
| | 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4.1 |
| | |
| | SUBMIT TWO SETS OF SHOP DRAWINGS THAT HAVE BEEN |
| | APPROVED BY THE DESIGNER OF RECORD FOR THE GLASS |
| | BALCONY AND STAIR GUARDS. |
| | |
| | 6) SUBMIT TWO SETS OF SHOP DRAWINGS THAT HAVE BEEN |
| | APPROVED BY THE DESIGNER OF RECORD FOR THE HOLLOW CORE |
| | PLANK INSTALLATION. |
| | |
| | 7) SUBMIT TWO COMPLETE SETS OF INSTALLATION |
| | INSTRUCTIONS FOR THE ELEVATOR. |
| | |
| | 8) SUBMIT TWO COMPLETE SETS OF INSTALLATION |
| | INSTRUCTIONS FOR THE OUTDOOR BBQ GRILL. |
| | |
| | 9) SUBMIT TWO COMPLETE SETS OF MANUALS WITH |
| | INSTALLATION INSTRUCTIONS FOR THE SPECIFIC MODEL OF |
| | SPARK MODERN FIRES INDOOR AND OUTDOOR LINEAR BURNER |
| | SYSTEMS THAT WILL BE INSTALLED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |