| 2015-03-03 13:39:49 | 1) SHT. A7.5 SHOWS THE HEIGHT OF THE GRAB BARS MEASURED |
| | TO THE CENTERLINE OF THE GRAB BARS. THE GRAB BARS SHALL |
| | BE MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2010 |
| | FAC SEC.609.4. |
| | 2) SHT. P.1 - THE PLAN REFERES TO CIVIL DRAWINGS FOR |
| | THE CONTINUATION OF THE STORM DRAIN.THE SUBMITTED CIVIL |
| | DRAWINGS DO NOT SHOW ANY STORM DRAIN/STORM SEWER |
| | PIPING. CLARIFY. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION |
| | INSTRUCTIONS FOR THE STEAM GENERATING UNIT.WPB AMEND. |
| | TO 2010 FBC SEC. 107.2.1. |
| | 4) SHT.P.1 - SHOWS A NOTE BY THE ELEVATOR STATING "4" |
| | STORM DRAIN FROM 2ND FLOOR" BUT NOTHING IS SHOWN. |
| | CLARIFY. |
| | 5) SHT.P.2 - SHOWS A NOTE BY THE ELEVATOR STATING "3" |
| | STORM DRAIN DOWN TO FIRST FLOOR BUT NOTHING IS |
| | SHOWN.CLARIFY. |
| | 6) THE PLUMBING FIXTURES SHOWN ON THE SANITARY RISER |
| | DIAGRAM MAKE IT A LITTLE DIFFICULT TO SEE THE SANITARY |
| | LINES AT PLACES. IF POSSIBLE, PLEASE DELETE THE FIGURES |
| | FROM THE SANITARY RISER DIAGRAM.WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1. |
| | 7) SHT. P.6 APPEARS TO SHOW ASHP #6 CONNECTED TO THE |
| | SANITARY SYSTEM. CLARIFY. |
| | 8) SHT. P.7 - INDICATE HOW THE HANGER RODS WILL BE |
| | CONNECTED TO THE BOTTOM OF THE CONCRETE SLAB.WPB AMEND. |
| | TO 2010 FBC SEC. 107.2.1. |
| | 9) SIZE ALL SECTIONS OF THE SANITARY RISERR.WPB AMEND. |
| | TO 2010 FBC SEC. 107.2.1. |
| | |
| | WATER |
| | 9) AN RPZ BACKFLOW PREVENTER IS REQUIRED ON THE WATER |
| | SERVICE AT THE METER. WPB CROSS CONNECTION MANUAL. |
| | 10) SHT. P.5 - IDENTIFY ALL THE FIXTURES/APPLIANCES |
| | CONNECTED TO THE WATER RISER IN THE CABANA BATH.WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 11) IDENTIFY THE LAUNDRY FIXTURES ON THE WATER RISER. |
| | WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 12) SHT. P.5 - THE V. SINK IS SHOWN ON THE WATER RISER |
| | BUT NOT SHOWN ON THE PLAN VIEW ON SHT.P.3.CLARIFY. |
| | 13) SHT. P.5 - GW-3 IS SHOWN ON SHT. P.3 BUT NOT ON P.5 |
| | - CLARIFY. |
| | 14) SHOW THE STEAM GENERATING UNIT ON THE WATER RISER |
| | IF APPLICABLE. |
| | 15) SIZE THE HOT WATER RETURN LINE ON SHT. P.5.WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 16) SHT. P.5 - THERE ARE VARIOUS SECTIONS OF THE WATER |
| | RISER THAT ARE NOT SIZED. SIZE THE RISER DIAGRAM AS |
| | NEEDED. ( SEE PIPE TO FIXTURES, BRANCH LINES, ETC.). |
| | |
| | STORM |
| | 17) INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAINAGE |
| | PIPE. |
| | 18) SHT. P.8 - THERE IS ONE ROOF DRAIN THAT IS NOT |
| | LABELED/IDENTIFIED ON THE RISER. CLARIFY.WPB AMEND. TO |
| | 2010 FBC SEC. 107.2.1. |
| | 19) SIZE ALL VERTICAL AND HORIZONTAL SECTIONS OF THE |
| | STORM DRAIN SYSTEM.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | |
| | GAS |
| | 21) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION |
| | INSTRUCTIONS FOR ALL GAS EQUIPMENT. EQUIPMENT SHALL BE |
| | LAISTED AND LABELED. 2010 FGC SEC. 301.3, 402.2. |
| | 22) SUBMIT MANUF . SPECIFICATIONS FOR THE VENTLESS |
| | PRESSURE REGULATORS.2010 FBCR SEC.G2421.3. |
| | 23) SUBMIT A SITE PLAN THAT SHOWS THE LOCATION OF THE |
| | LP TANK, DISTANCE FROM THE STRUCTURE, PROPERTY LINES |
| | TANK CAPACITY, ANCHORING, ETC. AND THE LOCATION OF ALL |
| | EXTERIOR GAS EQUIPMENT.WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | 24) SUBMIT DETAILS SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION POINTS OF ALL GAS VENTS PER 2010 FBCR |
| | SEC.G2407. |
| | 25) SHT. P.3 APPEARS TO SHOW PE GAS PIPNG UNDER THE |
| | SLAB.PE PIPE CAN ONLY BE USED UNDERGROUND OUTDOORS. |
| | FBCR SEC.G2415.15.1. PIPING UNDER A BUILDING SHALL BE |
| | ENCASED IN CONDUIT PER 2010 FBCR SEC.G2415.12. |
| | 26) SIZE THE GAS LINE TO APPLIANCES G-102, G-WH1, |
| | G-103, G-105.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 27) SHT. P.3 - IDENTIFY ALL THE GAS APPLIANCES ON THE |
| | GAS RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 28) P.7 NOTES APPLIANCE G-106 AS NATURAL GAS BUT SHT. |
| | P.3 REFERS TO LP GAS. CLARIFY. |
| | 29) THE SUBMITTED SPECS ON THE PA SHEETS FOR THE |
| | FIREPLACE LIST THE MAXIMUM BTU LOAD AS 39,000 AND THE |
| | SCHEDULE ON SHT.P.4 SHOWS 40,000. CLARIFY. INDICATE THE |
| | MODEL OF THE FIREPLACE BEING USED ON THE PA SHEEET. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |