Plan Review Notes
Plan Review Notes For Permit 15020495
Permit Number 15020495
Review Stop E
Sequence Number 1
Notes
Date Text
2015-03-24 12:38:053/24/2015
 PROJECT: WILLIAMS RESIDENCE
 PERMIT#: 15020495
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 220.16(2)
 PROVIDE A COMPLETE LOAD CALCULATION. LOADS FOR NEW
 CIRCUITS OR EXTENDED CIRCUITS IN PREVIOUSLY WIRED
 DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE WITH
 220.12 OR 220.14, AS APPLICABLE.
  
 2) NEC 702.5 CAPACITY AND RATING.
 A) INDICATE THE PROPOSED ATS HAS LOAD MANAGEMENT
 CAPABILITY WITH THE CAPACITY TO MANAGE THE LOAD THAT IS
 ILLUSTRATED BY THE LOAD CALCULATION TO BE OVER AND
 ABOVE THE ACTUAL CAPACITY OF THE PROPOSED GENERATOR OR
 INDICATE A GENERATOR AND ATS WITH THE CAPACITY TO
 TRANSFER AND CARRY THE TOTAL CONNECTED LOAD THAT IS
 ILLUSTRATED THE LOAD CALCULATION.
 B) A SEPARATE PERMIT APPLICATION ACCOMPANIED BY THE
 MANUFACTURER?S EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR THE GENERATOR SYSTEM.
  
 3) ADDITIONAL PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURER?S EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR ANY PROPOSED LOW VOLTAGE OR SPECIALTY
 SYSTEM SUCH AS ELEVATOR, SAUNA, MOTORIZED BLINDS,
 ACCESS CONTROL, MOTORIZED GATE, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, OR DATA, AND COMMUNICATION
 SYSTEMS.
  
 4) WPB AMENDMENTS TO FBC 107.3.2
 CLARIFY ROOM #118. IT IS INDICATED AS A WALK IN CLOSET
 OR A SAUNA.
  
 5) WPB AMENDMENTS TO FBC 107.3.2
 PROVIDE THE ELECTRICAL CIRCUITRY ON THE PLAN FOR ALL OF
 THE EXHAUST AND DRYER FANS.
  
 6) WPB AMENDMENTS TO FBC 107.3.2
 INDICATE THE LOCATION OF THE ?SMART BOX?
  
 7) NEC 250.94
 INDICATE THE LOCATION OF THE INTERSYSTEM BONDING STRIP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  