| 2015-02-18 12:29:05 | BUILDING PLAN REVIEW |
| | PERMIT: 15020493 |
| | ADD: 2656 ELECTRONICS WAY |
| | CONT: RAPP |
| | TEL: ( 561) 842-3299 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB.18/2015 |
| | ACTION: DENIED |
| | |
| | 1) THIS PROJECT QUALIFIES FOR A RESIDENT INSPECTOR |
| | UNDER THE 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| | SATISFIED AS TO |
| | THEIR QUALIFICATIONS AND RELIABILITY.THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE |
| | INCH |
| | |
| | 1A) (3) SETS OF PLANS WILL BE REQUIRED. |
| | |
| | 1B) THE RESIDENT INSPECTOR FORMS WILL NEED TO BE FILED |
| | OUT BY ALL REQUIRED PARTIES. FORMS WILL BE E-MAILED TO |
| | [email protected] |
| | |
| | 1C) LICENSURE FOR THE RESIDENT INSPECTOR AND RESUME. |
| | 110.3.7.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL |
| | INSPECTOR TO CONDUCT THE |
| | MINIMUM STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS |
| | REQUIRED BY THIS CODE, SECTION 553.73, FLORIDA |
| | STATUTES, WITHOUT DUPLICATIVE INSPECTION BY THE |
| | BUILDING DEPARTMENT. THE BUILDING OFFICIAL IS |
| | RESPONSIBLE FOR ENSURING THAT ANY PERSON CONDUCTING |
| | INSPECTIONS IS QUALIFIED AS A BUILDING INSPECTOR UNDER |
| | PART XII OF CHAPTER 468, FLORIDA STATUTES, OR CERTIFIED |
| | AS A SPECIAL INSPECTOR UNDER CHAPTER 471 OR 481, |
| | FLORIDA STATUTES. INSPECTIONS OF THRESHOLD BUILDINGS |
| | REQUIRED BY SECTION 553.79(5), FLORIDA STATUTES, ARE IN |
| | ADDITION TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | |
| | 1D) THE CONTRACTOR WILL ALSO NEED TO SEND IN A RESUME |
| | OF THERE PROJECTS ALSO, CONTACT INFO FOR KEN CONRAD THE |
| | MANAGER OF THE RESIDENT & THRESHOLD PROGRAMS: |
| | KEN CONRAD CONTACT INFORMATION: |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 1E) THE CONTRACTOR WILL STILL NEED TO CALL IN |
| | INSPECTIONS TO THE CITY FOR AUDITTING PURPOSES. |
| | |
| | 2) SHEET S1.0 SHOWS A SECTION 1/S2.0 SHOWS THE PROPOSED |
| | HELICAL PILE SS125 W/ (1) 14 INCH AND (1) 12 INCH |
| | HELICES THE PLANS DO NOT SHOW THE ACTUAL LOCATION WHERE |
| | THESE PILES ARE TO BE INSTALLED NOR MANUFACTURERS |
| | DESIGN LOADS. 2010 FBC-B 1810.3.1.5 HELICAL PILES. |
| | HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED IN |
| | ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICE TO RESIST |
| | ALL STRESSES INDUCED BY INSTALLATION INTO THE GROUND |
| | AND SERVICE LOADS. NOTE THERE IS NO SOILS REPORT |
| | PROVIDING THE MINIMUM BEARING VALUE OF THE SOILS. |
| | |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2/19/ 2015 CONTRACTOR BROUGHT IN THE NOC,PARTIAL |
| | RESIDENT INSPECTOR AGREEMENT & 3RD SET OF PLANS. JW |
| | |