2015-03-02 17:20:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET G - 010 INCORRECT REFERENCES TO THE CURRENT
 EDITION OF THE FIRE CODE. PLEASE CORRECT AND REFERENCE
 THAT THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS
 OF THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
  
 IT IS UNCLEAR ON THE SUBMITTED PLAN WHAT IS EXISTING.
 PLEASE CLEARLY INDICATE WHAT IS EXISTING AND WHAT IS
 PROPOSED. IF A NEW WALL IS BEING INSTALLED IT SHALL BE
 FIRE RATED ACCORDING TO THE SEPARATION REQUIREMENTS OF
 STORAGE AND BUSINESS/MERCANTILE.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 PLEASE MAKE REFERENCE TO THE FOLLOWING ON THE SUBMITTED
 PLAN:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  