Plan Review Notes
Plan Review Notes For Permit 15020476
Permit Number 15020476
Review Stop P
Sequence Number 1
Notes
Date Text
2015-03-14 05:06:551) SUBMIT A SANITARY AND WATER RISER FOR REVIEW THAT
 CLEARLY REFLECTS THE SCOPE OF WORK TO BE DONE. WPB
 AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 2) SUBMIT A PIPNG DIAGRAM FOR THE RELOCATED COMPRESSOR.
 SHOW TYPE OF PIPING, ALL DROPS, VALVES, ETC.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 3) SHT. M-2,1, - SUBMIT A RISER DIAGRAM FOR THE
 CONDENSATE PIPING SYSTEM. SHOW THE TERMINATION POINT OF
 THE SYTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) ALL HOSE BIBBS SHALL BE SEPARATELY VALVED PER THE
 2010 FPC SEC.606.2 (2).
 5) INDICATE THE SIZE OF THE ROOF GUTTER ON THE DOCK
 CANOPY. GUTTERS SHALL BE SIZED IN ACCORDANCE WITH TABLE
 1106.6 OF THE 2010 FPC.
 6) THE PLANS REFER TO GAS PIPING. SUBMIT A GAS PIPING
 RISER DIAGRAM FOR REVIEW.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 7) SUBMIT A ROOF DRAINAGE PLAN SHOWING THE SQUARE
 FOOTAGE OF THE ROOF DRAINED BY EACH DOWNSPOUT. THE SIZE
 OF THE DOWNSPOUTS SHALL COMPLY WITH TABLE 1106.2 (2).
 8) SHOW THE TERMINATION POINT OF THE RAIN WATER SYSTEM.
 THE ENGINEERING PLANS APPEAR TO BE INCONCLUSIVE. THE
 LEADERS DISCHARGE TO THE CATCH BASINS AND FROM THERE
 INTO RCP BUT I CANNOT DETERMINE WHERE THE FINAL
 DISCHARGE POINT IS. I ASSUME THE RETENTION BASINS BUT
 IT IS NOT CLEAR ON THE ENGINEERING PLAMS. CLARIFY.
 9) IF THERE IS A PARAPET WALL THEN ONE-HALF OF THE AREA
 OF ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF
 SHALL BE ADDED TO THE PROJECTED ROOF AREA FOR INCLUSION
 IN CALCULATING THE REQUIRED SIZE OF THE VERTICAL
 CONDUCTORS, LEADERS AND HORIZONTAL STORM DRAINAGE
 PIPING. 2010 FPC SEC.1106.4.
  