Plan Review Notes
Plan Review Notes For Permit 15020450
Permit Number 15020450
Review Stop P
Sequence Number 1
Notes
Date Text
2015-02-17 06:20:381) SHT. S-1 - THE PRINTING ON THIS SHEET IS VERY SMALL
 AND DIFFICULT TO READ. SUBMIT 2 CLEAR AND LEGIBLE
 COPIES. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT. S-1 - BOTH COPIES OF THIS PLAN SHALL BE SIGNED
 AND SEALED BY THE DESIGN PROFESSIONAL PER THE FLA.
 ADMINISTRATIVE CODE RULE 61G15-23.002.
 3) SUBMIT TWO COPIES OF THE FSEC CERTIFICATION AND OF
 THE PIPING DIAGRAM. WPB AMEND. TO 2010 FBC SEC. 107.1.
 4) SUBMIT A PIPING DIAGRAM / SCHEMATIC THAT CLEARLY
 SHOWS THE LOCATION OF ISOLATION VALVES AS REQUIRED BY
 THE 2010 FBCR SEC. M2301.2.8.ALSO, SUBMIT PIPING
 DIAGRAM/SCHEMATIC THAT SHOWS HOW THE SOLAR SYSTEM IS
 CONNECTED TO THE EXISTING POOL PIPING SYSTEM.
 5) SHOW THE LOCATION OF REQUIRED PRESSURE AND
 TEMPERATURE RELIEF VALVES. 2010 FBCR SEC.M2301.2.3.
 6) ANY CONNECTION OF THE SOLAR SYSTEM TO THE POTABLE
 WATER SYSTEM SHALL BE PROTECTED AGAINST BACKFLOW IN
 ACCORDANCE WITH 2010 FBCR SEC.M2301.5 & P2902.5.5.
  
 PLUMBING PLAN REVIEW