2016-02-17 16:55:584TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #15020419
 2/17/16
  
 1) REFER TO PAGE 3 OF THE ENERGY CALCULATION FORM
 506-2010: THE DESIGN PROFESSIONAL OF RECORD SHALL
 PROVIDE HIS/HER SIGNATURE ON THE DOCUMENT. A) PLEASE
 CLARIFY FROM WHAT STANDARD OR COMPLIANCE TABLE THE
 EFFICIENCY CRITERIA FOR THE AHU'S IS DERIVED FROM, AND
 HOW CAN THE DESIGN EFFICIENCY OF THE PROPOSED UNITS
 (1.10) BE LESS THAN THE REQUIRED EFFICIENCY CRITERIA
 (1.12) AND STILL PASS" B) PROVIDE COMPLIANCE DATA FOR
 THE FCU'S AND THE OAU-1.
 2) SHEET M5.3A: REFER TO SECTION 510.8 AND TABLE 510.8
 FBC-10 MECHANICAL AND INDICATE THE TYPE AND GAGE OF
 STEEL OF THE TWO HAZARDOUS EXHAUST DUCTS FOR THE
 NITROUS OXIDE AND NITROGEN STORAGE ROOMS.
 3) M7.01: IN RESPONSE TO COMMENT #4 FROM THE 1ST
 REVIEW, AND COMMENT #5 FROM THE 2ND REVIEW, THE
 ARCHITECT OF RECORD LESLIE D. BRUNELL HAS PROVIDED
 NOTES IN THE NARRATIVE RESPONSE TO CLARIFY THE
 MECHANICAL ROOM VENTILATION, AND REFRIGERATION
 DETECTION SYSTEM FUNCTIONS. PLEASE PLACE THESE NOTES
 AND THE VENTILATION CALCULATIONS ON SHEET M7.0.
 4) MP5.3A: INDICATE WHERE THE REFRIGERANT RELIEF VENT
 PIPING IS DISCHARGING TO.
 5) M0.4 & M5.3A: THE VENTILATION TABLE IS INDICATING
 275 CFM'S OF SUPPLY AIR FOR EACH DIFFUSER AT THE
 NITROUS OXIDE AND NITROGEN STORAGE ROOMS, HOWEVER THE
 PLAN INDICATES 325 CFM'S EACH.
 6) M8.3: PLEASE PROVIDE SPECIFICATIONS FOR THE CHILLED
 WATER AND STEAM PIPING ON THIS PLAN SHEET OR ONE OF THE
 OTHER MECHANICAL DETAIL PAGES.
 7) REFER TO COMMENT #20 FROM THE 3RD REVIEW: IN
 RESPONSE, THE ARCHITECT REFERENCES NOTE #4 ON SHEET
 M0.0. PLEASE REVISE THE NOTE TO INCLUDE ACCESS TO AC
 EQUIPMENT AND PROVIDE DIMENSIONED CONSTRUCTION DETAILS
 FOR THE ACCESS PANELS.
 8) M0.0, NOTE #29: PLEASE EXPAND THE NOTE TO INCLUDE
 DEFERRED SUBMITTALS FOR THE REFRIGERANT LEAK DETECTORS,
 THE DUCT SMOKE DETECTORS, THE ROOM PRESSURIZATION
 MONITORS AND CONTROL SENSORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  