| 2016-02-17 16:55:58 | 4TH REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15020419 |
| | 2/17/16 |
| | |
| | 1) REFER TO PAGE 3 OF THE ENERGY CALCULATION FORM |
| | 506-2010: THE DESIGN PROFESSIONAL OF RECORD SHALL |
| | PROVIDE HIS/HER SIGNATURE ON THE DOCUMENT. A) PLEASE |
| | CLARIFY FROM WHAT STANDARD OR COMPLIANCE TABLE THE |
| | EFFICIENCY CRITERIA FOR THE AHU'S IS DERIVED FROM, AND |
| | HOW CAN THE DESIGN EFFICIENCY OF THE PROPOSED UNITS |
| | (1.10) BE LESS THAN THE REQUIRED EFFICIENCY CRITERIA |
| | (1.12) AND STILL PASS" B) PROVIDE COMPLIANCE DATA FOR |
| | THE FCU'S AND THE OAU-1. |
| | 2) SHEET M5.3A: REFER TO SECTION 510.8 AND TABLE 510.8 |
| | FBC-10 MECHANICAL AND INDICATE THE TYPE AND GAGE OF |
| | STEEL OF THE TWO HAZARDOUS EXHAUST DUCTS FOR THE |
| | NITROUS OXIDE AND NITROGEN STORAGE ROOMS. |
| | 3) M7.01: IN RESPONSE TO COMMENT #4 FROM THE 1ST |
| | REVIEW, AND COMMENT #5 FROM THE 2ND REVIEW, THE |
| | ARCHITECT OF RECORD LESLIE D. BRUNELL HAS PROVIDED |
| | NOTES IN THE NARRATIVE RESPONSE TO CLARIFY THE |
| | MECHANICAL ROOM VENTILATION, AND REFRIGERATION |
| | DETECTION SYSTEM FUNCTIONS. PLEASE PLACE THESE NOTES |
| | AND THE VENTILATION CALCULATIONS ON SHEET M7.0. |
| | 4) MP5.3A: INDICATE WHERE THE REFRIGERANT RELIEF VENT |
| | PIPING IS DISCHARGING TO. |
| | 5) M0.4 & M5.3A: THE VENTILATION TABLE IS INDICATING |
| | 275 CFM'S OF SUPPLY AIR FOR EACH DIFFUSER AT THE |
| | NITROUS OXIDE AND NITROGEN STORAGE ROOMS, HOWEVER THE |
| | PLAN INDICATES 325 CFM'S EACH. |
| | 6) M8.3: PLEASE PROVIDE SPECIFICATIONS FOR THE CHILLED |
| | WATER AND STEAM PIPING ON THIS PLAN SHEET OR ONE OF THE |
| | OTHER MECHANICAL DETAIL PAGES. |
| | 7) REFER TO COMMENT #20 FROM THE 3RD REVIEW: IN |
| | RESPONSE, THE ARCHITECT REFERENCES NOTE #4 ON SHEET |
| | M0.0. PLEASE REVISE THE NOTE TO INCLUDE ACCESS TO AC |
| | EQUIPMENT AND PROVIDE DIMENSIONED CONSTRUCTION DETAILS |
| | FOR THE ACCESS PANELS. |
| | 8) M0.0, NOTE #29: PLEASE EXPAND THE NOTE TO INCLUDE |
| | DEFERRED SUBMITTALS FOR THE REFRIGERANT LEAK DETECTORS, |
| | THE DUCT SMOKE DETECTORS, THE ROOM PRESSURIZATION |
| | MONITORS AND CONTROL SENSORS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |