| 2015-12-14 09:29:16 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15020419 |
| | ADD: 1309 N. FLAGLER DR. / ADDITION |
| | 1300 N. DIXIE HWY. |
| | 74/43/43/15/19/001/0010 |
| | CONT: DE ANGELIS DIAMOND HEALTHCARE GROUP |
| | TEL: (239)594-1994 |
| | CONTACT: ??????? NOT FILLED IN ON FORM |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W * 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS |
| | ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | GOOD SAMARITAN MEDICAL CENTER O?KEEFEE TOWER VERTICAL |
| | ADDITION |
| | |
| | 3RD REVIEW |
| | DATE: MON. DEC. 14/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM |
| | BEACH ART IN PUBLIC PLACES ORDINANCE. |
| | |
| | 3) 3RD REQUEST: ASBESTOS: IN ACCORDANCE WITH SECTION |
| | 553.79 F. S. THIS IS TO ADVISE YOU OF THE OWNERS OR |
| | OPERATORS? RESPONSIBILITY TO COMPLY WITH THE STATE & |
| | FEDERAL ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 |
| | F. S. AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS |
| | INCLUDE- ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN |
| | NOTIFICATION TO THE DEPARTMENT OF ENVIRONMENTAL |
| | PROTECTION PRIOR TO: * DEMOLITION OF ALL REGULATED |
| | STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| | THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| | HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| | POLLUTION CONTROL SECTION) |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561)355-3070 |
| | |
| | 4) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 4A) COMPLIED. 109.3.6.1. STRUCTURAL INSPECTION PLAN. |
| | |
| | 4) COMPLIED: SPECIAL INSPECTOR FORMS. |
| | |
| | 4C) COMPLIED. STATEMENT: FLORIDA STATUTE: 553.79(7). |
| | |
| | 4D) COMPLIED: VOIDED RESUMES WERE SUBMITTED FOR EDDIE |
| | CARRETERO AND FOR WESLEY FOSTER E. I. NEITHER SHOWS |
| | LICENSURE AS A LICENSED INSPECTOR WITH A BN LICENSE, |
| | WHY ARE THEY SUBMITTED. NOT A P.E. OR BN. |
| | |
| | 4E) 3RD REQUEST. I?VE ASKED KEN CONRAD IF HE HAD A COPY |
| | OF THE CONTRACTORS EXPERIENCE, APPARENTLY WHEN KEN |
| | VIEWED THE ATTACHMENT HE HAD NOT PRINTED IT AND THE |
| | ATTACHMENT WAS DELETED, WE HAVE NO WRITTEN RECORD OF |
| | THE CONTRACTORS JOB HISTORY FOR THE FILE. 7/08/2015 |
| | E-MAIL FROM K. CONRAD ATTACHED INFORMATION WAS SENT TO |
| | KEN ON 5/21/15.THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS |
| | MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 4F)PROVISO: NOTICE ONLY, NO ACTION NEED TO BE TAKEN FOR |
| | PLAN REVIEW. PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 4G) PROVISO: NOTICE ONLY, NO ACTION NEED TO BE TAKEN |
| | FOR PLAN REVIEW. PLEASE CALL THE CITY OF WEST PALM |
| | BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS. |
| | |
| | 4H)PROVISO: NOTICE ONLY, NO ACTION NEED TO BE TAKEN FOR |
| | PLAN REVIEW. SECTION 109.3.6 THRESHOLD BUILDINGS, |
| | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. |
| | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 5) COMPLIED. FLOOD ZONE. VERTICAL ADDITION NOT IN FLOOD |
| | ZONE. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. LETTER SUBMITTED AND ACCEPTED FOR A (4) |
| | HOUR FIRE WALL SEPARATING VERTICAL ADDITION FROM THE |
| | REMAINDER OF THE BUILDING. |
| | |
| | 8) COMPLIED. |
| | |
| | 9-11) COMPLIED, 107.3.4.2 DEFERRED SUBMITTALS. PRODUCT |
| | APPROVALS. PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS |
| | & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 12-17A-C) COMPLIED. |
| | |
| | 17D & E) BUILDING PROVISO: DUMBWAITER MANUFACTURER |
| | SPECIFICATIONS AND SHOP DRAWINGS ARE REQUIRED PROVIDING |
| | CODE COMPLIANCE WITH 2010 FBC-B 708.14 ELEVATOR, |
| | DUMBWAITER AND OTHER HOIST WAYS & TABLE 715.4. |
| | |
| | |
| | 17F, 17G, 18A) COMPLIED. |
| | |
| | 18B) BUILDING PROVISO: DUMBWAITER MANUFACTURER |
| | SPECIFICATIONS AND SHOP DRAWINGS ARE REQUIRED PROVIDING |
| | CODE COMPLIANCE WITH 2010 FBC-B 708.14 ELEVATOR, |
| | DUMBWAITER AND OTHER HOISTWAYS & TABLE 715.4. |
| | |
| | 18C) . COMPLIED. |
| | |
| | 19) SHEET A5.5A : |
| | |
| | 19A) NOT APPLICABLE, REMOVED FROM THE SCOPE OF WORK. |
| | ROOFING UNDER SEPARATE PERMIT. |
| | |
| | 19B-C) BUILDING PROVISO: DUMBWAITER MANUFACTURER |
| | SPECIFICATIONS AND SHOP DRAWINGS ARE REQUIRED PROVIDING |
| | CODE COMPLIANCE WITH 2010 FBC-B 708.14 ELEVATOR, |
| | DUMBWAITER AND OTHER HOIST WAYS & TABLE 715.4. |
| | |
| | 19D) COMPLIED |
| | |
| | 20-23) COMPLIED |
| | |
| | 24) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 25) DIGITAL REVIEW. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |