Plan Review Notes
Plan Review Notes For Permit 15020419
Permit Number 15020419
Review Stop P
Sequence Number 2
Notes
Date Text
2015-07-12 09:12:281) SHT. A11.7 - DETAILS 20 & 21 SHOW EMERGENCY OVERFLOW
 SCUPPERS WITH THE BOTTOM OF THE SCUPPERS LEVEL WITH THE
 ROOF. SECTION 1503.4.2.1 REQUIRES THAT OVERFLOW
 SCUPPERS BE LOCATED IN WALLS OR PARAPETS NOT LESS THAN
 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 COVERING.
 2) SHT.A11.3 - DETAIL # 4 SHOWS WHAT APPEARS TO BE A
 SUMP IN THE NEW ELEVATOR SHAFTS.IF THE ELEVATORS ARE
 HYDRAULIC, THEN AN OIL SEPARATOR IS REQUIRED PER THE
 2010 FPC SEC.1003.4. SUBMIT DETAILS FOR THE SEPARATOR
 AND SHOW THE LOCATION ON THE PLANS. THE SEPARATOR SHALL
 COMPLY WIT 2010 FPC SECTIONS 1003.4.2 - 1003.4.2.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  