| Plan Review Notes For Permit 15020419 |
| Permit Number |
15020419 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-12 09:12:28 | 1) SHT. A11.7 - DETAILS 20 & 21 SHOW EMERGENCY OVERFLOW | | | SCUPPERS WITH THE BOTTOM OF THE SCUPPERS LEVEL WITH THE | | | ROOF. SECTION 1503.4.2.1 REQUIRES THAT OVERFLOW | | | SCUPPERS BE LOCATED IN WALLS OR PARAPETS NOT LESS THAN | | | 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF | | | COVERING. | | | 2) SHT.A11.3 - DETAIL # 4 SHOWS WHAT APPEARS TO BE A | | | SUMP IN THE NEW ELEVATOR SHAFTS.IF THE ELEVATORS ARE | | | HYDRAULIC, THEN AN OIL SEPARATOR IS REQUIRED PER THE | | | 2010 FPC SEC.1003.4. SUBMIT DETAILS FOR THE SEPARATOR | | | AND SHOW THE LOCATION ON THE PLANS. THE SEPARATOR SHALL | | | COMPLY WIT 2010 FPC SECTIONS 1003.4.2 - 1003.4.2.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|