| 2015-07-22 11:17:14 | 2ND REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15020419 |
| | |
| | THE 1ST REVIEW COMMENTS HAVE BEEN ADDRESSED HOWEVER THE |
| | PLANS HAVE BEEN REVIEWED A SECOND TIME TO CHECK FOR |
| | REQUESTED CORRECTIONS AND ADDITIONAL CODE COMPLIANCES. |
| | PLEASE REVISE THE PLANS IN ACCORDANCE WITH THE |
| | FOLLOWING LIST OF COMMENTS. |
| | |
| | 1) THE SUBMITTED FLORIDA ENERGY EFFICIENCY COMPLIANCE |
| | FORM 506-2010 DOES NOT PROVIDE ANY COMPLIANCE DATA FOR |
| | THE CHILLERS, THE COOLING TOWER, AND AHU-4 & AHU-4-1. |
| | SEE TABLES 503.2.3 (4) 503.2.3(7) & 503.2.3(8) FBC-10 |
| | ENERGY CONSERVATION. PLEASE REVISE ACCORDINGLY. |
| | 2) COOLING AND HEATING EQUIPMENT SIZING CALCULATIONS |
| | HAVE NOT BEEN SUBMITTED- REFERENCE SECTION 503.2.1 |
| | FBC-10 ENERGY AND PROVIDE THE CALCULATIONS IN |
| | ACCORDANCE WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL |
| | N. |
| | 3) COOLING TOWER: A) SUBMIT MARLEY PRODUCT DATA AND |
| | DIAGRAM CUT SHEETS WITH THE ENGINEER OF RECORD'S |
| | APPROVAL STAMP AND SIGNATURE ON THE DOCUMENTS. B) |
| | PROVIDE ENGINEERED STRUCTURAL DETAILS AND WIND LOAD |
| | DESIGN CRITERIA FOR ATTACHMENT OF THE COOLING TOWER AND |
| | TOWER BASE TO THE ROOF STRUCTURE- SECTION301.12 FBC-10 |
| | MECHANICAL. C) PROVIDE STRUCTURAL DETAILS FOR |
| | INSTALLATION OF THE TOWER LADDER AND GUARDRAILS. D) |
| | SHOW THE PHYSICAL LOCATIONS OF THE COOLING TOWER |
| | CHEMICAL FEED PUMPS AND CHEMICAL STORAGE DRUMS AS SHOWN |
| | IN THE DETAIL ON SHEET M8.1. PROVIDE ALL REQUIRED |
| | DETAILS FOR SECURE MOUNTING OF THE PUMP EQUIPMENT AND |
| | THE 55 GALLON DRUMS. |
| | 4) CHILLERS AND ASHRAE 15 COMPLIANCE: A) SUBMIT TRANE |
| | MANUFACTURER'S SPECIFICATIONS SHEETS WITH THE ENGINEER |
| | OF RECORD'S APPROVAL STAMP AND SIGNATURE ON THE |
| | DOCUMENTS. B) INDICATE THE TYPE AND QUANTITY OF |
| | REFRIGERANT LBS. IN THE EQUIPMENT SCHEDULES FOR THE |
| | CHILLERS ON SHEET M0.1- SEE TABLE 1103.1 FBC-10 |
| | MECHANICAL. C) REFER TO ASHRAE 15 AND SECTION 1105 FOR |
| | MECHANICAL RM 303: SHOW THE LOCATION OF THE REFRIGERANT |
| | LEAK DETECTOR, PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | DEVICE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. D) |
| | PROVIDE VENTILATION CALCULATIONS FOR NORMAL VENTILATION |
| | OF THE MECHANICAL ROOM, AND CALCULATIONS FOR EMERGENCY |
| | CONDITIONS, AND INDICATE COMPLIANCE. E) PROVIDE DETAILS |
| | FOR MAKE-UP AND EXHAUST VENTILATION AIR INCLUDING |
| | LOCATIONS OF AIR INLET AND EXHAUST OUTLETS, FANS |
| | SCHEDULES, LOUVER, CLEARANCE DISTANCES SIZES ETC. F) |
| | PROVIDE A SEQUENCE OF OPERATION FOR THE LEAK DETECTION |
| | /VENTILATION SYSTEM THAT INCLUDES A DESCRIPTIVE |
| | NARRATIVE OF THE PROCESS AND A DIAGRAM. G) PROVIDE |
| | DETAILS FOR PURGE DISCHARGE PIPING INCLUDING THE PIPING |
| | RUN AND DISCHARGE LOCATION- REFER TO SECTION 1105.7. H) |
| | SEE SHEET M7.06: CLARIFY WHY THERE IS NO DATA |
| | PERFORMANCE DATA LISTED IN THE DIAGRAM FOR CH-2. PLEASE |
| | NOTE THAT SHEET M7.06 IS IDENTIFIED INCORRECTLY IN THE |
| | INDEX AS "EXHAUST FAN CONTROL DIAGRAMS". |
| | 5) SHEET M0.4 & M0.5: INDICATE ON THE PLANS WHICH |
| | CURRENT CODE OR DESIGN STANDARD WAS USED TO CALCULATE |
| | THE REQUIRED VENTILATION AND AIR BALANCES FOR ROOMS AND |
| | SPACES INCLUDING PRESSURIZATION CALCULATIONS FOR THE |
| | OR?S AND ISOLATIONS ROOMS ETC. |
| | 6) PROVIDE EQUIPMENT SCHEDULES FOR THE AIR INTAKE AND |
| | EXHAUST LOUVER LISTING MAKES AND MODELS, DIMENSIONS, |
| | AND FREE AIR SPACE FOR EACH. PROVIDE SIZING |
| | CALCULATIONS FOR THE O/A INTAKES, AND SUBMIT SPECS FOR |
| | ALL REQUIRED AIR FILTERS REVIEWED AND APPROVED BY THE |
| | ENGINEER OF RECORD. |
| | 7) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| | DUCTS TO BE INSTALLED REVIEWED AND APPROVED BY THE |
| | ENGINEER OF RECORD- REFER TO SECTION 419.3.6.4 FBC-10 |
| | BUILDING. INDICATE THE FLEX DUCT SIZES ON THE PLANS AND |
| | SHOW INSTALLATION DETAILS INCLUDING A DETAIL FOR |
| | CONNECTION TO THE OR ROOM DIFFUSERS. |
| | 8) PROVIDE STRUCTURAL DETAILS FOR HANGING AND SUPPORT |
| | OF THE AIR HANDLERS AND FAN COIL UNITS. |
| | 9) PROVIDE CHILLED WATER AND STEAM PIPE SPECIFICATIONS |
| | AND DETAILS FOR INSTALLATION AND SUPPORT. |
| | 10) PROVIDE DETAILS FOR CONDENSATE DISPOSAL FROM THE |
| | AIR HANDLERS. INDICATE THE TYPES AND SIZES OF PIPING, |
| | THE PIPING RUNS, AND DISCHARGE LOCATIONS- SEE SECTION |
| | 307 FBC-10 MECHANICAL. SHOW DETAILS FOR SECONDARY OR |
| | AUXILIARY DISPOSAL PER SECTION 307.2.3. |
| | 11) PROVIDE WIND LOAD ENGINEERING FOR MOUNTING THE ROOF |
| | TOP EXHAUST FANS- SECTION 301.12. PLEASE NOTE THAT |
| | INLINE BOOSTER FANS FOR THE DRYERS ARE PROHIBITED BY |
| | THE WPB FIRE DEPT. |
| | 12) SHEET M5.3.A, NITROUS OXIDE AND NITROGEN STORAGE |
| | ROOMS 326 A & B: REVISE THE PLANS WITH NOTES AND |
| | DETAILS TO SHOW COMPLIANCE WITH THE FOLLOWING SECTIONS |
| | OF NFPA 99. SECTION 9.3.6.5.3.1- CONTINUOUS |
| | VENTILATION, 9.3.6.5.2- RATE OF VENTILATION |
| | CALCULATION, 9.3.6.5.3.3- LOCATION OF EXHAUST VENT IN |
| | THE ROOM, AND 9.3.6.5.3.2- TYPE OF MAKE-UP AIR AND |
| | EXHAUST DUCTWORK, AND EXHAUST DUCT TERMINATION |
| | CLEARANCES. A) PLEASE NOTE THAT DAMPERS ARE REQUIRED |
| | FOR THE EXHAUST DUCTS PENETRATING THE FIRE RATED WALLS |
| | OF THE STORAGE ROOMS UNLESS THE EXHAUST SYSTEM IS |
| | DEFINED AS HAZARDOUS- REFER TO SECTION 510.6.1 |
| | MECHANICAL. REVISE THE PLANS TO SHOW COMPLIANCE |
| | 13) M5.3.A: VENTILATION IS REQUIRED FOR GENERATOR RM |
| | 340. PLEASE PROVIDE CALCULATIONS AND DETAILS ON THE |
| | PLAN. |
| | 14) M5.3.A: MISSING FIRE DAMPERS AT DUCTS PENETRATING |
| | THE EXHAUST SHAFT AT 321-B CORRIDOR. |
| | 15) M5.3.A: NUMEROUS BRANCH DUCT SIZES ARE NOT SHOWN: |
| | PLEASE REVIEW AND REVISE. |
| | 16) M5.4.A: MISSING FIRE DAMPER AT RETURN AIR DUCT |
| | PENETRATING THE FIRE RATED CORRIDOR WALL AT THE NE |
| | CORNER OF MECH. RM 404. |
| | 17) M5.5.A: A) LABEL THE DAMPERS PENETRATING THE SHAFTS |
| | AT CORRIDOR 573. B) MANY DAMPERS MISSING FOR DUCTS |
| | PENETRATING RATED CORRIDOR 541 & 542 WALLS, AND THE |
| | SATELLITE PHARMACY WALLS. |
| | 18) M5.5.A: THE OR ROOM NUMBERS DO NOT MATCH THE OR |
| | NUMBERS IN THE SCHEDULE ON SHEET M0.3. |
| | 19) M5.5.A: THE SAV AND RAV NUMBERS ON THE PLAN DO NOT |
| | MATCH THE NUMBERS IN THE SCHEDULE- M0.3. |
| | 20) REQUIRED SUBMITTALS, NOA'S AND FL. PRODUCT |
| | APPROVALS TO BE REVIEWED AND APPROVED BY THE ENGINEER |
| | OF RECORD: EXHAUST AND INTAKE LOUVERS, ROOF MOUNTED |
| | EXHAUST FANS, FLEX DUCTS, FIRE AND FIRE/SMOKE DAMPERS, |
| | DUCT SMOKE DETECTORS, REFRIGERANT LEAK DETECTORS, HEPA |
| | EQUIPMENT AND FILTERS. |
| | 21) PLEASE REVIEW SECTION 503.2.9 FBC-10 ENERGY |
| | CONSERVATION FOR SYSTEM COMPLETION AND TESTING AND |
| | BALANCING- AND PROVIDE NOTES ON THE PLAN TO INDICATE |
| | HOW COMPLIANCE WILL BE MET. |
| | |