Plan Review Notes
Plan Review Notes For Permit 15020419
Permit Number 15020419
Review Stop E
Sequence Number 2
Notes
Date Text
2015-12-28 19:47:12THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. PG. AS3.1: PLEASE MAKE THE SITE PLAN LEGEND
 DIFFERENT TO MAKE IDENTIFICATION OF EXISTING VS. NEW
 WORK SIMPLER.
 2. PG. E0.0: 2010 FBC-E SECTION 502.3.8, RECESSED
 LUMINARIES INSTALLED IN THE BUILDING THERMAL ENVELOPE
 SHALL BE IC RATED & SEAL TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 3. PG. EL4.1B, EL4.3A, EL4.4A, EL4.5A, EP4.1B, EP4.3A,
 EP4.4A, EP4.5A, EL5.1B, EL5.3A, EL5.4A, EL5.5A, EL5.6A,
 EP4.1B, EP4.3A, EP4.4A, EP4.5A, EP5.1B, EP5.3A, EP5.4A,
 EP5.5A, EP5.6A, EP5.7A: PLEASE MAKE THE DEMOLITION
 LEGEND DIFFERENT TO MAKE IDENTIFICATION OF EXISTING TO
 REMAIN VS. EXISTING TO BE REMOVED. THIS PAGE CAN?T BE
 PROPERLY REVIEWED AS THE BOUNDARY BETWEEN EXISTING TO
 REMAIN VS. EXISTING TO BE REMOVED IS NOT CLEARLY
 DEFINED.
 4. PG. EL5.1B, EL5.3A, EL5.4A, EL5.5A, EL5.6A: IN
 ADDITION TO HAVING THE SAME ISSUES AS COMMENT THREE (3)
 ABOVE, I WAS UNABLE TO LOCATE WITHIN THE SET OF
 DRAWINGS A LIGHTING DIAGRAM INDICATING COMPLIANCE WITH
 THE MANDATORY SWITCHING AND CONTROL REQUIREMENTS OF THE
 ENERGY CONSERVATION CODE. A MORE DETAILED EXAMINATION
 WILL BE CONDUCTED ON THE ENLARGED AREA SHEETS.
 5. PG. EL5.1B, EL5.3A, EL5.4A, EL5.5A, EL5.6A: REFER TO
 LIFE SAFETY SHEET FOR EXIT LIGHT PLACEMENT.
 6. PG. EP5.1B, EP5.1B: ADDRESSES FIRST LEVEL OF AN AREA
 B THAT IS NOT PREVIOUSLY IDENTIFIED ON THE SITE PLAN OR
 KEYPLAN.
 7. PG. EP5.3A: IDENTIFY THE SD ENCLOSED INSIDE A
 DIAMOND.
 8. PG. EP5.7A: NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT
 RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN
 ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15- AND 20-AMPERE,
 125- AND 250-VOLT NONLOCKING RECEPTACLES SHALL BE
 LISTED WEATHER-RESISTANT TYPE ?WR?.
 9. ALL EY SHEETS ADDRESS FIRE ALARM SYSTEMS, WHICH
 SHALL BE ON A SEPARATE SUBMITTAL AND THEREFORE HAVE NOT
 BEEN REVIEWED.
 10. PG. E6.1, E6.2, E6.3, E6.4: NEC 110.26(D)
 ILLUMINATION. ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS,
 AND PANELBOARDS. THIS ILLUMINATION SHALL BE ON THE
 EMERGENCY CIRCUIT. NOTE: FIRE AND BLDG. MAY HAVE AN
 ISSUE WITH THE SWING OF THE DOORS OF THE ELECTRICAL
 EQUIPMENT ROOMS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  