| 2015-07-01 06:45:25 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15020419 |
| | ADD: 1309 N. FLAGLER DR. / ADDITION |
| | 1300 N. DIXIE HWY. |
| | 74/43/43/15/19/001/0010 |
| | CONT: TBD |
| | TEL: (239)594-1994 |
| | CONTACT: ??????? NOT FILLED IN ON FORM |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | GOOD SAMARITAN MEDICAL CENTER O?KEEFEE TOWER VERTICAL |
| | ADDITION |
| | 2ND REVIEW |
| | DATE: TUES. JUNE 30/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM |
| | BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT |
| | APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR |
| | WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER |
| | 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST |
| | PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC |
| | PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE |
| | ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION |
| | COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS |
| | |
| | 3) 2ND REQUEST: ASBESTOS: IN ACCORDANCE WITH SECTION |
| | 553.79 F. S. THIS IS TO ADVISE YOU OF THE OWNERS OR |
| | OPERATORS? RESPONSIBILITY TO COMPLY WITH THE STATE & |
| | FEDERAL ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 |
| | F. S. AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS |
| | INCLUDE- ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN |
| | NOTIFICATION TO THE DEPARTMENT OF ENVIRONMENTAL |
| | PROTECTION PRIOR TO: * DEMOLITION OF ALL REGULATED |
| | STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | |
| | FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| | THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| | HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| | POLLUTION CONTROL SECTION) |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561)355-3070 |
| | |
| | 4) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 4A)COMPLIED> 109.3.6.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A (WRITTEN/ TYPED) SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| | TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| | BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 4B) SEMI-COMPLIED. PAGE 4 LEFT BLANK, TO BE FILED OUT |
| | BY THE CERTIFIED INSPECTION CO. & OWNER. |
| | PAGE 5 LEFT BLANK TO BE FILED OUT BY ALL (3) ENTITIES, |
| | CONTRACTOR, ARCHITECT AND ENGINEER OF RECORD AND |
| | NOTARIZED. |
| | THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. FORMS MUST BE FILED OUT AND |
| | RETURNED TO THE BUILDING DEPARTMENT CAN ISSUE A PERMIT. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | FORMS WERE E-MAILED TO: [email protected] |
| | 4/28/2015 08:32 AM |
| | |
| | 4C) 2ND REQUEST. THE THRESHOLD BLDG., REQUIRED |
| | STATEMENT: |
| | |
| | FLORIDA STATUTE: 553.79(7)(D) ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND CHAPTER |
| | 633. |
| | |
| | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 4D)SEMI COMPLIED. RESUMES WERE SUBMITTED FOR EDDIE |
| | CARRETERO AND FOR WESLEY FOSTER E. I. NEITHER SHOWS |
| | LICENSURE AS A LICENSED INSPECTOR WITH A BN LICENSE, |
| | WHY ARE THEY SUBMITTED. |
| | |
| | FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 4E) COMPLIED. 7/08/2015 E-MAIL FROM K. CONRAD ATTACHED |
| | INFORMATION WAS SENT TO KEN ON 5/21/15. |
| | THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| | KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected] |
| | |
| | 4F) NOTICE ONLY, NO ACTION NEED TO BE TAKEN FOR PLAN |
| | REVIEW. PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. |
| | FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT |
| | LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH |
| | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| | THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS. |
| | |
| | 4G) NOTICE ONLY, NO ACTION NEED TO BE TAKEN FOR PLAN |
| | REVIEW. PLEASE CALL THE CITY OF WEST PALM BEACHES? |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 4H) NOTICE ONLY, NO ACTION NEED TO BE TAKEN FOR PLAN |
| | REVIEW. SECTION 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 5)2ND REQUEST. THE SUBMITTED SURVEY DOES NOT INDICATE |
| | THE DEMARCATION LINES REPRESENTING THE A, B, & C FLOOD |
| | ZONES LOCATED ON THIS PROPERTY. WITH THIS INFORMATION |
| | WE WILL BE ABLE TO DETERMINE IF THE BUILDING ITSELF IS |
| | IN THE FLOOD ZONE A OR OUT OF IT. THIS NEEDS TO BE |
| | DETERMINED FOR DOCUMENTATION IF SUBSTANTIAL IMPROVEMENT |
| | IS GOING TO BE A FACTOR IN THE UPCOMING REVIEW. THIS |
| | PROPERTY IS LOCATED IN AN A5 FLOOD ZONE. FBC BUILDING |
| | 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| | ADDITIONAL 6 INCHES OF ELEVATION. |
| | |
| | 5A) DURING THE PERMITTING OF THIS STRUCTURE THERE WILL |
| | BE REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31/2015 |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM. |
| | |
| | 5B) THIS SUBMITTAL A SURVEYS WAS SUBMITTED, PLEASE NO |
| | DOCUMENTATION WAS SUBMITTED IF THE BUILDING LOWEST |
| | LEVEL IS BELOW THE 7 FT. -6 IN. NGVD THE REQUIREMENTS |
| | FOR FLOOD PROOFING CITY MUNI CODE SECTION 94-546(B)(2) |
| | NONRESIDENTIAL CONSTRUCTION AND SECTION 94-611 |
| | DEFINITIONS FOR SUBSTANTIAL IMPROVEMENTS. |
| | 5C) 2010 FBC-B 419.4.2.2.2 FOR ALL EXISTING FACILITIES, |
| | THE LOWEST FLOOR ELEVATIONS OF ALL ADDITIONS, AND ALL |
| | PATIENT SUPPORT AREAS INCLUDING FOOD SERVICE, AND ALL |
| | PATIENT SUPPORT UTILITIES, INCLUDING MECHANICAL, AND |
| | ELECTRICAL (EXCEPT FUEL STORAGE AS NOTED IN SECTION |
| | 419.4.2.9.3 OF THIS CODE) FOR THE ADDITIONS SHALL BE AT |
| | OR ABOVE THE ELEVATION OF THE EXISTING BUILDING, IF THE |
| | EXISTING BUILDING WAS DESIGNED AND CONSTRUCTED TO |
| | COMPLY WITH EITHER THE SITE STANDARDS OF SECTION 419.4 |
| | OF THIS CODE OR LOCAL FLOOD RESISTANT REQUIREMENTS IN |
| | EFFECT AT THE TIME OF CONSTRUCTION, WHICHEVER REQUIRES |
| | THE HIGHER ELEVATION, UNLESS OTHERWISE PERMITTED BY |
| | SECTION 1612 OF THIS CODE. IF THE EXISTING BUILDING WAS |
| | CONSTRUCTED PRIOR TO THE ADOPTION OF EITHER THE SITE |
| | STANDARDS OF 419.4 OF THIS CODE OR LOCAL FLOOD |
| | RESISTANT REQUIREMENTS, THEN THE ADDITION AND ALL |
| | PATIENT SUPPORT AREAS AND UTILITIES FOR THE ADDITION AS |
| | DESCRIBED IN THIS SECTION SHALL EITHER BE DESIGNED AND |
| | CONSTRUCTED TO MEET THE REQUIREMENTS OF SECTION |
| | 419.4.2.2.1 OF THIS CODE OR BE DESIGNED AND CONSTRUCTED |
| | TO MEET THE DRY FLOOD PROOFING REQUIREMENTS OF SECTION |
| | 1612 OF THIS CODE. |
| | |
| | 6) SEMI-COMPLIED. |
| | 6.4 2010 FBC-EXISTING BLDG. CODE CHAPTER 10 |
| | |
| | 7) COMPLIED> PLEASE PROVIDE A SURVEY OF THE EXISTING |
| | SITE. ZONING COMMENT OF THE FOOTPRINT OF THE EXISTING |
| | BUILDINGS CAN NOT BE INCREASED. PLEASE PROVIDE THE |
| | SURVEY SO A COMPARISON OF THE PROPOSED VERTICAL |
| | ADDITION AND EXISTING BUILDING CAN BE COMPARED, |
| | VERTICAL ADDITIONS VERSES HORIZONTAL ADDITIONS. |
| | |
| | 2010 EXISTING BLDG. CODE 1001.2 CREATION OR EXTENSION |
| | OF NONCONFORMITY. |
| | AN ADDITION SHALL NOT CREATE OR EXTEND ANY |
| | NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE |
| | ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY, |
| | STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR |
| | THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL |
| | SYSTEMS. |
| | EXST. BLDG. CODE 1002.1 HEIGHT LIMITATIONS. |
| | 1002.2 AREA LIMITATIONS. |
| | 1002.3 FIRE PROTECTION SYSTEMS. |
| | |
| | EXST. BLDG. CODE 1001.3 OTHER WORK. ANY REPAIR OR |
| | ALTERATION WORK WITHIN AN EXISTING BUILDING TO WHICH AN |
| | ADDITION IS BEING MADE SHALL COMPLY WITH THE APPLICABLE |
| | REQUIREMENTS OF THE APPROPRIATE CHAPTER OF THIS CODE |
| | FOR THE LEVEL OF REHABILITATION UNDERTAKEN. |
| | |
| | 8) 2010 FL. EXISTING BUILDING CODE PLEASE SHOW |
| | COMPLIANCE WITH: |
| | |
| | 8A) 2ND REQUEST. PLEASE PROVIDE THE ORIGINAL DOCUMENTS |
| | SHOWING THIS STRUCTURE WAS ORIGINALLY DESIGNED FOR THE |
| | ADDITIONAL STORIES. WE ARE LOOKING AT A ACCUMULATIVE |
| | LOADING OF THE FOUNDATIONS AND COLUMNS. WE UNDERSTAND |
| | THAT THIS IS TO BE IN THE FUTURE A 10 STORY HIGH-RISE. |
| | IF THESE DOCUMENTS CANNOT BE PRODUCED THEN A STRUCTURAL |
| | ANALYSIS MUST BE COMPLETED TO THE 2010 FBC-B. EXST. |
| | BLDG. CODE 1003.2 ADDITIONAL GRAVITY LOADS. EXISTING |
| | STRUCTURAL ELEMENTS SUPPORTING ANY ADDITIONAL GRAVITY |
| | LOADS AS A RESULT OF ADDITIONS SHALL COMPLY WITH THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | EXCEPTIONS: 1. STRUCTURAL ELEMENTS WHOSE STRESS IS NOT |
| | INCREASED BY MORE THAN 5 PERCENT. |
| | |
| | 8B)2ND REQUEST, THE RESPONSE INDICATES THAT A LATERAL |
| | ANALYSIS WAS PREFORMED, PLEASE PROVIDE THE ANALYSIS FOR |
| | REVIEW AND CODE COMPLIANCE. EXST. BLDG. CODE 1003.3 |
| | LATERAL-FORCE-RESISTING SYSTEM. THE |
| | LATERAL-FORCE-RESISTING SYSTEM OF EXISTING BUILDINGS TO |
| | WHICH ADDITIONS ARE MADE SHALL COMPLY WITH SECTIONS |
| | 1003.3.1, 1003.3.2 AND 1003.3.3. |
| | EXCEPTIONS: 1003 (2.) IN OTHER EXISTING BUILDINGS WHERE |
| | THE LATERAL-FORCE STORY SHEAR IN ANY STORY IS NOT |
| | INCREASED BY MORE THAN 10 PERCENT CUMULATIVE. |
| | |
| | 8C) 2ND REVIEW. PLEASE SEE SHEET S5.1 CODES AND |
| | STANDARDS WIND LOADS WERE DESIGNED TO 180 MPH VULT AND |
| | C EXPOSURE. |
| | |
| | 8C)(1) COMPLIED> WIND DESIGN TO 170 MPH VULT. PLEASE |
| | REVIEW THE 2010 FBC-B TABLE 1604.5 RISK CATEGORY OF |
| | BUILDINGS AND OTHER STRUCTURES. RISK CATEGORY IV |
| | STRUCTURES INCLUDE GROUP I-2 OCCUPANCIES AND OTHER |
| | STRUCTURES DESIGNED AS ESSENTIAL FACILITIES HAVING |
| | SURGERY OR EMERGENCY TREATMENT FACILITIES. PLEASE |
| | REVIEW THE 2010 FBC-B TABLE 1609B FOR RISK CATEGORY III |
| | AND IV BUILDINGS AND STRUCTURES. THE FIGURE SHOWS THIS |
| | LOCATION AS A 180 MPH, VULT WIND ZONE. |
| | |
| | 2010 FBC-B 419.3 N ADDITION TO THE CODES AND STANDARDS |
| | REFERENCED IN SECTION 419.2 OF THIS CODE, THE FOLLOWING |
| | MINIMUM STANDARDS OF CONSTRUCTION AND SPECIFIED MINIMUM |
| | ESSENTIAL FACILITIES, SHALL APPLY TO ALL NEW HOSPITALS |
| | AND ALL ADDITIONS, ALTERATIONS OR RENOVATIONS TO AN |
| | EXISTING LICENSED HOSPITAL, AS DESCRIBED IN SECTION |
| | 419.1 OF THIS CODE AND LISTED IN SECTION 419.3 OF THIS |
| | CODE. |
| | |
| | 8C)(2) 2ND REQUEST. SHEET S5.1 WIND DESIGN OF C |
| | EXPOSURE. WHEN YOU SHOOT A VECTOR TO THE N.E. TO PALM |
| | BEACH A DISTANCE OF OVER 5,040 FT. OF WATER IS |
| | ENCOUNTERED. ON THIS SAME VECTOR FROM THE FRONT OF THE |
| | BUILDING TO THE N.E. YOU ENCOUNTER 509 FT. OF |
| | SHORELINE, THEN THE 5,040 FT. OF WATER OF THE BUILDING. |
| | THIS MEETS THE REQUIREMENTS FOR EXPOSURE D. THE |
| | RESPONSE COMMENTS TAKEN FROM ASCE 7-10 PAGE 518 ARE TO |
| | BE TAKEN FOR THE MWFRS NOT COMPONENTS AND CLADDING. |
| | |
| | THE LAST PARAGRAPH OF THE STATED SECTION STATES, WIND |
| | LOADS FOR CLADDING AND LOW-RISE BUILDING ELEMENTS ARE |
| | DETERMINED USING THE UPWIND EXPOSURE FOR THE SINGLE |
| | SURFACE ROUGHNESS IN ONE OF THE EIGHT SECTORS OF FIG. |
| | C26.7.5 THAT GIVES THE HIGHEST CLADDING PRESSURE. |
| | |
| | EVEN IF YOU ARE IN A TRANSITION ZONE BETWEEN 2 SURFACE |
| | ROUGHNESS CLASSIFICATION, YOU USE THE HIGHER PRESSURES |
| | FOR THAT ZONE. |
| | |
| | 2010 FBC-B 1609.4.3. EXPOSURE D. EXPOSURE D SHALL APPLY |
| | WHERE THE GROUND SURFACE ROUGHNESS, AS DEFINED BY |
| | SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION |
| | FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 |
| | TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER. |
| | EXPOSURE D SHALL EXTEND INLAND FROM THE SHORELINE FOR A |
| | DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE HEIGHT OF |
| | THE BUILDING, WHICHEVER IS GREATER FROM AN EXPOSURE D |
| | CONDITION AS DEFINED IN THE PREVIOUS SENTENCE. |
| | |
| | FBC-B HOSPITALS. 419.4.2.3 STRUCTURAL STANDARDS. |
| | WIND LOAD DESIGN OF THE BUILDING STRUCTURE AND EXTERIOR |
| | ENVELOPE INCLUDING EXTERIOR WALL SYSTEMS SHALL BE |
| | DESIGNED IN ACCORDANCE WITH THE CODE. |
| | |
| | 9)2ND REQUEST. THE RESPONSE IS NOT CLEAR, DOES EITHER |
| | THE DESIGNER OF RECORD OR THE ARCHITECT WISH TO HAVE |
| | THE PRODUCT APPROVALS BE DEFERRED SUBMITTALS OR IS THE |
| | LIST ON THE FRONT PAGE WHAT IS GOING TO BE SUBMITTED |
| | FOR REVIEW. IF YOU WISH THE PRODUCT APPROVALS TO BE |
| | PART OF THE REVIEW, PLEASE SUBMIT THE COMPLETE PRODUCT |
| | APPROVALS IN THE VIEW FOLDER SECTION OF PROJECT DOX. |
| | PLEASE IDENTIFY ON ALL PRODUCT APPROVALS FOR, TYPE OF |
| | UNIT, SOME APPROVALS HAVE MORE THAN ONE MODEL IN THE |
| | APPROVAL, GLAZING, SIZES OF OPENINGS, TYPE OF GLAZING, |
| | IF MULLIONS ARE REQUIRED, IF THEY REQUIRE |
| | REINFORCEMENT, FASTENERS AND ASSOCIATED PRESSURES FOR |
| | THE OPENINGS. |
| | FOR THE ROOFING PRODUCT APPROVALS PLEASE CIRCLE THE |
| | SUB-SYSTEM OF THE APPROVAL, REVIEW THE ASSOCIATED |
| | PRESSURES AND IF ENHANCED FASTENING IS REQUIRED AND IF |
| | THE LIMITATIONS WILL ALLOW IT. |
| | |
| | PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 9A) 2010 FBC-B 419.4.2.4 ROOFING STANDARDS. |
| | 419.4.2.4.1 |
| | ROOFING MEMBRANE MATERIAL SHALL RESIST THE UPLIFT |
| | FORCES SPECIFIED IN THE CODE. ROOF COVERINGS SHALL BE |
| | INSTALLED ACCORDING TO THE SPECIFICATIONS PROVIDED BY |
| | THE MANUFACTURER. |
| | 419.4.2.4.2 LOOSE-LAID BALLASTED ROOFS SHALL NOT BE |
| | PERMITTED. |
| | |
| | 419.4.2.4.3 ALL NEW ROOF APPENDAGES SUCH AS DUCTS, |
| | TANKS, VENTILATORS, RECEIVERS, DX CONDENSING UNITS AND |
| | DECORATIVE MANSARD ROOFS AND THEIR ATTACHMENT SYSTEMS |
| | SHALL BE STRUCTURALLY ENGINEERED TO MEET THE WIND LOAD |
| | REQUIREMENTS OF THE APPLICABLE BUILDING CODE. ALL OF |
| | THESE ATTACHMENT SYSTEMS SHALL BE CONNECTED DIRECTLY TO |
| | THE UNDERLYING ROOF STRUCTURE OR ROOF SUPPORT |
| | STRUCTURE. |
| | |
| | 9B)2ND REQUEST. PLEASE REVIEW THIS SECTION, LARGE |
| | MISSILE IMPACT WINDOWS ARE REQUIRED. |
| | 2010 FBC-B 419.4.2.5 EXTERIOR UNIT STANDARDS. |
| | 419.4.2.5.1 |
| | ALL EXTERIOR WINDOW UNITS, SKYLIGHTS, EXTERIOR LOUVERS |
| | AND EXTERIOR DOOR UNITS INCLUDING VISION PANELS AND |
| | THEIR ANCHORING SYSTEMS SHALL BE IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF THE TESTING APPLICATION STANDARDS (TAS) |
| | 201, 202, AND 203 OF THIS CODE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF SECTIONS 1626.2 THROUGH 1626.4 OF THIS |
| | CODE. THE IMPACT RESISTANT COVERINGS MAY BE EITHER |
| | PERMANENTLY ATTACHED OR MAY BE REMOVABLE IF STORED ON |
| | SITE OF THE FACILITY. |
| | |
| | 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) ONCE THE WIND DESIGN & PRESSURES ARE CODE COMPLIANT |
| | IF EITHER THE DESIGNER OF RECORD OR CONTRACTOR WOULD |
| | PREFER TO SUBMIT THE PRODUCT APPROVALS AFTER THE |
| | ISSUANCE OF THE PERMIT THROUGH: |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 12) COMPLIED. |
| | |
| | 13A-D) COMPLIED. |
| | |
| | 13E)2ND REQUEST. IF THE HOSPITAL PERSONNEL ARE GOING TO |
| | PERFORM THE FIRE WATCH, PLEASE INDICATE THAT DURING THE |
| | FIRE WATCH THERE WILL BE NO OTHER DUTIES ASSIGNED TO |
| | THESE PERSONNEL AND ALSO PROVIDE WHAT LEVEL OF TRAINING |
| | THEY HAVE HAD TO PERFORM THE DUTIES OF A FIRE WATCH. |
| | HAVE THEY PERFORMED THESE DUTIES BEFORE, WHERE AND FOR |
| | HOW LONG? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | PLEASE NOTE THE FIRE DEPARTMENT HAS THE RIGHT TO REVOKE |
| | THIS PRIVILEGE AND ASSIGN PERSONNEL FOR THE FIRE WATCH, |
| | IF THE PERSONNEL ON FIRE WATCH ARE DERELICT IN THEIR |
| | DUTIES. |
| | |
| | COMMENT 1ST REVIEW. PLEASE PROVIDE WHICH OPTION THE |
| | SITE HAS CHOSEN AS AN OPTION, SHOW COMPLIANCE WITH; |
| | FBC-B 419.4.2.10.1 IF THE FACILITY REQUIRES FIRE |
| | SPRINKLERS AS PART OF ITS FIRE PROTECTION, EITHER OF |
| | THE FOLLOWING SHALL BE MET: AND WHO WILL PERFORM THE |
| | FIRE WATCH IF THIS METHOD IS CHOSEN. |
| | |
| | 14)2ND REQUEST. SEMI-COMPLIED. THE DESIGNER OF RECORD |
| | HAS PUT NUMERICALLY NUMBERED IDENTIFICATION TAGS FOR |
| | THE TEMPORARY STAIRS & BACK HOIST BUT THERE ARE NO KEY |
| | NOTES THAT ASSOCIATE WITH THESE NUMBERS. WHEN YOU WALK |
| | OUT OF EITHER THE VERTICAL EXIT STAIR # 15 OR THE EXIT |
| | DOORWAY 41 THERE APPEARS TO BE NO PROTECTION OVER THIS |
| | AREA FROM FALLING OBJECTS. |
| | |
| | COMMENT FROM 1ST REVIEW. SHEET 017-A1.1 VS. A1.2, |
| | SHEET018- A1.2 THE 2ND LEVEL SHOWS A TEMPORARY STAIR |
| | TOWER AND TEMPORARY BUCK-HOIST LOCATION NOT SHOWN ON |
| | THE 1ST FLOOR PLANS. PLEASE PROVIDE HOW WILL THE |
| | OCCUPANTS BE PROTECTED DURING CONSTRUCTION AND IN |
| | COMPLIANCE WITH FBC-B 3306.7 COVERED WALKWAYS. THE |
| | TEMPORARY STAIRS DOES NOT ADDRESS THIS ISSUE OF THE |
| | EXITING OF THE 1ST FLOOR. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) 2ND REQUEST. THE RESPONSE LETTER INDICATES THERE |
| | ARE KEY NOTES THAT ARE ASSOCIATED WITH THE NUMERICALLY |
| | NUMBERED IDENTIFICATION TAGS, THESE NOTES ARE MISSING |
| | FROM THESE SHEETS 017-A1.1 & 018-A.1.2. |
| | |
| | COMMENT FROM 1ST REVIEW. SHEET A1.2 ALSO INDICATES THAT |
| | THIS EXIT WILL BE TEMPORARILY CLOSED AND THE EXIT SIGN |
| | REMOVED. PLEASE PROVIDE A CODE COMPLIANT EXIT PLAN |
| | DURING THE TIME THE EXIT WILL NOT BE AVAILABLE. IN |
| | ESSENCE IT CREATES A DEAD END FOR BOTH THE NORTH AND |
| | SOUTH CORRIDORS. FBC-B 1018.4. |
| | |
| | 17) LIFE SAFETY SHEET A1.3 & SHEET A5.3A SHOW 1 HOUR |
| | FIRE RATED WALLS: |
| | |
| | 17A-C) COMPLIED. |
| | |
| | 17D & E) BUILDING PROVISO: DUMBWAITER MANUFACTURER |
| | SPECIFICATIONS AND SHOP DRAWINGS ARE REQUIRED PROVIDING |
| | CODE COMPLIANCE WITH 2010 FBC-B 708.14 ELEVATOR, |
| | DUMBWAITER AND OTHER HOISTWAYS & TABLE 715.4. |
| | |
| | 17F)COMPLIED. |
| | |
| | 17G) THE RESPONSE INDICATES THE WALL THAT SEPARATES THE |
| | ATRIUM FROM THE FUTURE HIGH RISE PORTION OF THE |
| | BUILDING, IS A 4 HOUR FIRE WALL SEPARATING THE |
| | STRUCTURE INTO 2 SEPARATE BUILDING. DOES THIS ALSO MEAN |
| | THAT ALL OF THE DOORS IN THIS 4 HOUR RATED WALL ARE 3 |
| | HOUR FIRE RATED ASSEMBLIES, DOORS AND FRAMES? AND MEET |
| | ALL OF THE REQUIREMENTS NO GLAZING IN THESE DOOR UNITS |
| | AND NO SIDELIGHTS? |
| | |
| | 1ST REVIEW COMMENT. NOTE DOES THE OVERLOOK 330 & 569 |
| | HAVE 1 HOUR PROTECTION IS THIS CONSIDERED PART OF AN |
| | ATRIUM? THERE IS NO 2ND FLOOR PLANS IN THE 500 SERIES |
| | DRAWINGS IS THIS A ATRIUM A 3 STORY ATRIUM REQUIRING |
| | SMOKE CONTROL A NOTE ON THE PLANS INDICATES A PRIVATE |
| | BRIDGE BELOW? FBC-B 404.5. SHEET A5.5A THE 5TH LEVEL, |
| | SECTION 404.6 EXCEPTION # 3 ONLY ALLOWS FOR THE |
| | ADJACENT SPACES OF ANY THREE FLOORS OF THE ATRIUM SHALL |
| | NOT BE REQUIRED TO BE SEPARATED FROM THE ATRIUM WHERE |
| | SUCH SPACES ARE ACCOUNTED FOR IN THE DESIGN OF THE |
| | SMOKE CONTROL SYSTEM. NOTE THIS IS THE 5TH LEVEL OF THE |
| | BUILDING. |
| | |
| | 18-18A) COMPLIED |
| | |
| | 18B) BUILDING PROVISO: DUMBWAITER MANUFACTURER |
| | SPECIFICATIONS AND SHOP DRAWINGS ARE REQUIRED PROVIDING |
| | CODE COMPLIANCE WITH 2010 FBC-B 708.14 ELEVATOR, |
| | DUMBWAITER AND OTHER HOISTWAYS & TABLE 715.4. |
| | 18C) . COMPLIED. |
| | 19) SHEET A5.5A : |
| | |
| | 19A) NOT APPLICABLE, REMOVED FROM THE SCOPE OF WORK. |
| | |
| | 19B-C) BUILDING PROVISO: DUMBWAITER MANUFACTURER |
| | SPECIFICATIONS AND SHOP DRAWINGS ARE REQUIRED PROVIDING |
| | CODE COMPLIANCE WITH 2010 FBC-B 708.14 ELEVATOR, |
| | DUMBWAITER AND OTHER HOISTWAYS & TABLE 715.4. |
| | |
| | 19D) COMPLIED |
| | |
| | 20-23) COMPLIED |
| | |
| | 24) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |