| 2015-04-28 13:20:50 | 1) PROVIDE A SCUPPER DETAIL FOR THE EMERGENCY RAIN |
| | WATER SYSTEM. SCUPPERS SHALL BE LOCATED PER SEC. |
| | 1503.4.2.1 OF 2010 FBC AND SHALL HAVE AN OPENING |
| | DIMENSION NOT LESS THAN 4 INCHES. 2010 FPC SEC.1107.3. |
| | 2) SUBMIT DOCUMENTATION THAT 1/2 THE AREA OF ANY |
| | VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF HAS |
| | BEEN ADDED TO THE PROJECTED ROOF AREA FOR THE SIZING OF |
| | THE ROOF DRAINS AND SCUPPERS. 2010 FPC SEC.1106.4. |
| | 3) SHT. A16.1 - GENERAL NOTES #3 - STATES EVERY 3' X 3' |
| | SHOWER SHALL RECEIVE GRAB BAR 10 G. THERE IS NO SIZE |
| | LISTED FOR THIS GRAB BAR. CLARIFY. |
| | 4) SHT. A16.1 - THE LOCATION OF THE TOILET PAPAER |
| | DISPENSERS IN THE ACCESSIBLE TOILET ROOMS SHALL COMPLY |
| | WITH 2010 FAC SEC.604.7. |
| | 5) SHT. 16.1 - ACCESSIBLE SINK IN COUNTER - TOE |
| | CLEARANCE SHALL BE PROVIDED COMPLYING WITH 2010 FAC |
| | SEC.306.2. |
| | 6) SHT. A16.1 - THE 30" X 60" ACCESSIBLE LISTS GRAB BAR |
| | 10F. THIS GRAB BAR IS NOT LISTED IN GRAB BAR LIST # 10 |
| | ALTHOUGH IT IS SHOWN IN THE ACCESSORY MOUNTING HEIGHTS. |
| | CLARIFY. |
| | 7) SHT. A16.1 - 30" X 60" ACCESSIBLE SHOWER ELEVATION |
| | SHOWS THE CONTROLS 48 INCHES TO THE BOTTOM. THE |
| | CONTROLS SHALL BE MEASURED 48 INCHES MAX TO THE TOP OF |
| | THE CONTROLS. 2010 FAC SEC.608.5.2. |
| | 8) SHT. A16.3. - APPEARS TO SHOW THE DOOR SWINGING INTO |
| | THE CLEAR FLOOR SPACE FOR THE LAVATORY.DOORS SHALL NOT |
| | SWING INTO THE CLEAR FLOOR SPACE FOR ANY FIXTURE. SEE |
| | EXCEPTION #2 IN FAC SEC.603.2.3. |
| | 9) SHT. A17.1 & A 17.2 - STAFF LOUNGE # 318 ( DETAIL |
| | 7S) & 518 (DETAIL 21W) - THE MAXIMUM HEIGHT OF THE SINK |
| | COUNTERS SHALL BE 34 INCHES PER 2010 FAC SEC.606.3. |
| | 10) SHT.A17.4 - WAITING AREA 609A (DETAIL 46S ) THE |
| | SINK COUNTER SHALL BE A MINIMUM OF 34 INCHES HIGH. FAC |
| | SEC. 606.3. |
| | 11) SHT. A17.5 - STAFF LOUNGE #636 - DETAIL 52S - SINK |
| | SHALL COMPLY WITH 2010 FAC SEC.606.3. |
| | 12) SHT. A16.2 - THE BAR SINKS IN THE PATIENT ROOMS |
| | SHALL COMPLY W/ 2010 FAC SEC.212.3. |
| | 13) SHT. A6.5A - OBJECTS WITH LEADING EDGES MORE THAN |
| | 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FINISH |
| | FLOOR SHALL NOT PROJECT MORE THAN 4 INCHES HORIZONTALLY |
| | INTO THE CIRCULATION PATH. SEE THE DRINKING FOUNTAINS |
| | ON 5TH FLR.IN PASSAGEWAY #567 (CHECK LEADING EDGE OF |
| | THE HIGH LEVEL UNIT). |
| | 14) SHT.A5.4A - SUBMIT DOCUMENTATION/CALCULATIONS FOR |
| | THE RAINWATER COLLECTION SYSTEM FOR THE NEW LOWER ROOF |
| | THAT COLLECTS THE RUNOFF FROM THE UPPER ROOF. INCLUDE |
| | 1/2 THE AREA OF ANY VERTICAL WALL TO THE PROJECTED ROOF |
| | AREA. 2010 FPC SEC.1106.4. |
| | 15) SHT. A5.4A - THE SINK AT THE COFFEE STATION IN |
| | PASSAGEWAY 415 SHALL BE COMPLY W/ FAC SEC. 606.3. |
| | 16) SHT. A5.5A - TOILET ROOM 528 - THE DOOR APPEARS TO |
| | BE SWINGING INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORIES.DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE FOR ANY FIXTURE. SEE EXCEPTION #2 IN FAC |
| | SEC.603.2.3. |
| | 17) SHT. A5.3A - THE DOORS APPEAR TO SWING INTO THE |
| | CLEAR FLOOR SPACE FOR TOILET ROOMS 319A & 319.B.DOORS |
| | SHALL NOT SWING INTO THE CLEAR FLOOR SPACE FOR ANY |
| | FIXTURE. SEE EXCEPTION #2 IN FAC SEC.603.2.3. |
| | 18) SHT.A6.6A - TOILET ROOMS 621A & 610B - THE DOORS |
| | APPREAR TO SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORIES. COMPLY WITH FAC SEC.603.2.3. SEE EXCEPTION |
| | #2. |
| | 19) SHT.A6.6A - SINK IN STAFF LOUNGE # 636 SHALL COMPLY |
| | W/ FAC SEC.606.3. |
| | 20) IN ALL GANG RESTROOMS, WHERE LAVATORIES ARE |
| | PROVIDED AT LEAST ONE SHALL COMPLY W/ FAC SEC. 606 AND |
| | SHALL NOT BE LOCATED IN A TOILET COMPARTMENT PER THE |
| | 2010 FAC SEC.213.3.4. |
| | 21) SHT.A9.1 - IT APPEARS THE OVERFLOW SCUPPERS FOR THE |
| | 6TH FLOOR ROOF DISCHARGE ONTO THE 3RD FLOOR ROOF. THE |
| | 3RD FLOOR ROOF DRAINAGE SYSTEM SHALL BE SIZED TO HANDLE |
| | THE ADDITIONAL DRAINAGE. THIS ALSO APPEARS TO OCCUR ON |
| | THE UPPER ROOFS DISCHARGING TO THE LOWER ROOFS. |
| | CLARIFY. |
| | 22) SHT. MG4.4A - CARIFY EXACTLY WHAT IS BEING REMOVED |
| | FROM THIS AREA. |
| | 22) SHT.P4.3A - THE 6" RWL IS ALSO NOTED AS A 2" VENT. |
| | CLARIFY. |
| | 24) SHT.P4.3A - SHOWS A RAINWATER LINE PENETRATING THE |
| | THE STAIR ENCLOSURE. THIS IS NOT PERMITTED PER THE 2010 |
| | FBC SEC.1022.3, 1022.4. THIS IS ALSO SHOWN ON SHT. |
| | P5.6A. |
| | 25) SHT. P5.7A DOES SHOW ANY PROVISION FOR EEMERGENCY |
| | DRAINAGE FOR THE STAIR EXTENSION TO THE ROOF. CLARIFY. |
| | 26) SHT. P6.2 - THE SQUARE FOOTAGE DRAINED GOES FROM |
| | 2701 SQ. FT. TO 2107 SQ. FT. THIS IS AN OBVIOUS TYPO |
| | ERROR. PLEASE CORRECT. |
| | 27) INDICATE THE SLOPE OF THE RAINWATER PIPING. COMPLY |
| | W/2010 FPC TABLE 1106.3 FOR THE HORIZONTAL STORM |
| | DRAINAGE PIPING. |
| | 28) PLEASE IDENTIFY THE AREAS ON THE STORM WATER RISER. |
| | IT IS EXTREMELY DIFFICULT TO CORRELATE THE PIPING WITH |
| | THE APPLICABLE AREAS. |
| | 29) SIZE ALL SECTIONS OF THE VENTING SYSTEM ON THE |
| | SANITARY ISOMETRIC. COMPLY WITH 2010 FPC TABLE |
| | 916.1.WPB AMEND. TO 2010 107.3.5.1.3. |
| | 30) SHT. P6.4 - IDENTIFY THE FIXTURES ON THE WATER |
| | RISER. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| | 31) ALL HOSE BIBBS SHALL BE VALVED PER FPC SEC.606.2. |
| | 32) THE PLANS SHOW NEW HYDRAULIC ELEVATORS BEING |
| | INSTALLED. AN OIL SEOARATOR IS REQUIRED N THE PIT IN |
| | ACCORDANCEWITH THE 2010 FPC SEC.1003.4. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |