Plan Review Notes
Plan Review Notes For Permit 15020419
Permit Number 15020419
Review Stop P
Sequence Number 1
Notes
Date Text
2015-04-28 13:20:501) PROVIDE A SCUPPER DETAIL FOR THE EMERGENCY RAIN
 WATER SYSTEM. SCUPPERS SHALL BE LOCATED PER SEC.
 1503.4.2.1 OF 2010 FBC AND SHALL HAVE AN OPENING
 DIMENSION NOT LESS THAN 4 INCHES. 2010 FPC SEC.1107.3.
 2) SUBMIT DOCUMENTATION THAT 1/2 THE AREA OF ANY
 VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF HAS
 BEEN ADDED TO THE PROJECTED ROOF AREA FOR THE SIZING OF
 THE ROOF DRAINS AND SCUPPERS. 2010 FPC SEC.1106.4.
 3) SHT. A16.1 - GENERAL NOTES #3 - STATES EVERY 3' X 3'
 SHOWER SHALL RECEIVE GRAB BAR 10 G. THERE IS NO SIZE
 LISTED FOR THIS GRAB BAR. CLARIFY.
 4) SHT. A16.1 - THE LOCATION OF THE TOILET PAPAER
 DISPENSERS IN THE ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH 2010 FAC SEC.604.7.
 5) SHT. 16.1 - ACCESSIBLE SINK IN COUNTER - TOE
 CLEARANCE SHALL BE PROVIDED COMPLYING WITH 2010 FAC
 SEC.306.2.
 6) SHT. A16.1 - THE 30" X 60" ACCESSIBLE LISTS GRAB BAR
 10F. THIS GRAB BAR IS NOT LISTED IN GRAB BAR LIST # 10
 ALTHOUGH IT IS SHOWN IN THE ACCESSORY MOUNTING HEIGHTS.
 CLARIFY.
 7) SHT. A16.1 - 30" X 60" ACCESSIBLE SHOWER ELEVATION
 SHOWS THE CONTROLS 48 INCHES TO THE BOTTOM. THE
 CONTROLS SHALL BE MEASURED 48 INCHES MAX TO THE TOP OF
 THE CONTROLS. 2010 FAC SEC.608.5.2.
 8) SHT. A16.3. - APPEARS TO SHOW THE DOOR SWINGING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY.DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE FOR ANY FIXTURE. SEE
 EXCEPTION #2 IN FAC SEC.603.2.3.
 9) SHT. A17.1 & A 17.2 - STAFF LOUNGE # 318 ( DETAIL
 7S) & 518 (DETAIL 21W) - THE MAXIMUM HEIGHT OF THE SINK
 COUNTERS SHALL BE 34 INCHES PER 2010 FAC SEC.606.3.
 10) SHT.A17.4 - WAITING AREA 609A (DETAIL 46S ) THE
 SINK COUNTER SHALL BE A MINIMUM OF 34 INCHES HIGH. FAC
 SEC. 606.3.
 11) SHT. A17.5 - STAFF LOUNGE #636 - DETAIL 52S - SINK
 SHALL COMPLY WITH 2010 FAC SEC.606.3.
 12) SHT. A16.2 - THE BAR SINKS IN THE PATIENT ROOMS
 SHALL COMPLY W/ 2010 FAC SEC.212.3.
 13) SHT. A6.5A - OBJECTS WITH LEADING EDGES MORE THAN
 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FINISH
 FLOOR SHALL NOT PROJECT MORE THAN 4 INCHES HORIZONTALLY
 INTO THE CIRCULATION PATH. SEE THE DRINKING FOUNTAINS
 ON 5TH FLR.IN PASSAGEWAY #567 (CHECK LEADING EDGE OF
 THE HIGH LEVEL UNIT).
 14) SHT.A5.4A - SUBMIT DOCUMENTATION/CALCULATIONS FOR
 THE RAINWATER COLLECTION SYSTEM FOR THE NEW LOWER ROOF
 THAT COLLECTS THE RUNOFF FROM THE UPPER ROOF. INCLUDE
 1/2 THE AREA OF ANY VERTICAL WALL TO THE PROJECTED ROOF
 AREA. 2010 FPC SEC.1106.4.
 15) SHT. A5.4A - THE SINK AT THE COFFEE STATION IN
 PASSAGEWAY 415 SHALL BE COMPLY W/ FAC SEC. 606.3.
 16) SHT. A5.5A - TOILET ROOM 528 - THE DOOR APPEARS TO
 BE SWINGING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORIES.DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE FOR ANY FIXTURE. SEE EXCEPTION #2 IN FAC
 SEC.603.2.3.
 17) SHT. A5.3A - THE DOORS APPEAR TO SWING INTO THE
 CLEAR FLOOR SPACE FOR TOILET ROOMS 319A & 319.B.DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE FOR ANY
 FIXTURE. SEE EXCEPTION #2 IN FAC SEC.603.2.3.
 18) SHT.A6.6A - TOILET ROOMS 621A & 610B - THE DOORS
 APPREAR TO SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORIES. COMPLY WITH FAC SEC.603.2.3. SEE EXCEPTION
 #2.
 19) SHT.A6.6A - SINK IN STAFF LOUNGE # 636 SHALL COMPLY
 W/ FAC SEC.606.3.
 20) IN ALL GANG RESTROOMS, WHERE LAVATORIES ARE
 PROVIDED AT LEAST ONE SHALL COMPLY W/ FAC SEC. 606 AND
 SHALL NOT BE LOCATED IN A TOILET COMPARTMENT PER THE
 2010 FAC SEC.213.3.4.
 21) SHT.A9.1 - IT APPEARS THE OVERFLOW SCUPPERS FOR THE
 6TH FLOOR ROOF DISCHARGE ONTO THE 3RD FLOOR ROOF. THE
 3RD FLOOR ROOF DRAINAGE SYSTEM SHALL BE SIZED TO HANDLE
 THE ADDITIONAL DRAINAGE. THIS ALSO APPEARS TO OCCUR ON
 THE UPPER ROOFS DISCHARGING TO THE LOWER ROOFS.
 CLARIFY.
 22) SHT. MG4.4A - CARIFY EXACTLY WHAT IS BEING REMOVED
 FROM THIS AREA.
 22) SHT.P4.3A - THE 6" RWL IS ALSO NOTED AS A 2" VENT.
 CLARIFY.
 24) SHT.P4.3A - SHOWS A RAINWATER LINE PENETRATING THE
 THE STAIR ENCLOSURE. THIS IS NOT PERMITTED PER THE 2010
 FBC SEC.1022.3, 1022.4. THIS IS ALSO SHOWN ON SHT.
 P5.6A.
 25) SHT. P5.7A DOES SHOW ANY PROVISION FOR EEMERGENCY
 DRAINAGE FOR THE STAIR EXTENSION TO THE ROOF. CLARIFY.
 26) SHT. P6.2 - THE SQUARE FOOTAGE DRAINED GOES FROM
 2701 SQ. FT. TO 2107 SQ. FT. THIS IS AN OBVIOUS TYPO
 ERROR. PLEASE CORRECT.
 27) INDICATE THE SLOPE OF THE RAINWATER PIPING. COMPLY
 W/2010 FPC TABLE 1106.3 FOR THE HORIZONTAL STORM
 DRAINAGE PIPING.
 28) PLEASE IDENTIFY THE AREAS ON THE STORM WATER RISER.
 IT IS EXTREMELY DIFFICULT TO CORRELATE THE PIPING WITH
 THE APPLICABLE AREAS.
 29) SIZE ALL SECTIONS OF THE VENTING SYSTEM ON THE
 SANITARY ISOMETRIC. COMPLY WITH 2010 FPC TABLE
 916.1.WPB AMEND. TO 2010 107.3.5.1.3.
 30) SHT. P6.4 - IDENTIFY THE FIXTURES ON THE WATER
 RISER. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 31) ALL HOSE BIBBS SHALL BE VALVED PER FPC SEC.606.2.
 32) THE PLANS SHOW NEW HYDRAULIC ELEVATORS BEING
 INSTALLED. AN OIL SEOARATOR IS REQUIRED N THE PIT IN
 ACCORDANCEWITH THE 2010 FPC SEC.1003.4.
  
  