Plan Review Notes
Plan Review Notes For Permit 15020419
Permit Number 15020419
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-06 13:06:49PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS WITH THE PLAN.PER
 SECTION 503.2.1 CALCULATION OF HEATING AND COOLING
 2010 FLORIDA ENERGY CODE.
 2) MISSING FIRE DAMPERS IN CORRIDOR 327 AND ELEVATOR
 LOBBY. MISSING MULTIPLE FIRE DAMPERS THROUGH OUT THE
 PLAN
 607.5.2 FIRE BARRIERS 2010 FBC (M)
 3) REFER TO SECTION 607.5.5 SHAFT ENCLOSURES 2010 FBC
 (M)
 4) THERE ARE TWO 10" PIPES OR DUCT FROM THE CHASE TO
 THE
 EMERG GENERATOR ROOM PLEASE EXPLAIN
 5) SHOW ALL RATED WALLS ON MECHANICAL PLANS. PER
 SECTION
 107 2010 FBC
 6) NOTE #1 PAGE M5.3A RELOCATING EXISTING DRYER DUCT
 CITY OF WEST PALM BEACH FIRE DEPARTMENT WILL NOT PERMIT
 BOOSTER FANS.
 7) REFER TO SECTION 304.11 GUARDS
 8) REFER TO SECTION 301.12 WIND RESISTANCE FOR
 EQUIPMENT
 ON THE ROOF. 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  