| Plan Review Notes For Permit 15020419 |
| Permit Number |
15020419 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-06 13:06:49 | PLAN DENIED | | | 1) PROVIDE ENERGY CALCULATIONS WITH THE PLAN.PER | | | SECTION 503.2.1 CALCULATION OF HEATING AND COOLING | | | 2010 FLORIDA ENERGY CODE. | | | 2) MISSING FIRE DAMPERS IN CORRIDOR 327 AND ELEVATOR | | | LOBBY. MISSING MULTIPLE FIRE DAMPERS THROUGH OUT THE | | | PLAN | | | 607.5.2 FIRE BARRIERS 2010 FBC (M) | | | 3) REFER TO SECTION 607.5.5 SHAFT ENCLOSURES 2010 FBC | | | (M) | | | 4) THERE ARE TWO 10" PIPES OR DUCT FROM THE CHASE TO | | | THE | | | EMERG GENERATOR ROOM PLEASE EXPLAIN | | | 5) SHOW ALL RATED WALLS ON MECHANICAL PLANS. PER | | | SECTION | | | 107 2010 FBC | | | 6) NOTE #1 PAGE M5.3A RELOCATING EXISTING DRYER DUCT | | | CITY OF WEST PALM BEACH FIRE DEPARTMENT WILL NOT PERMIT | | | BOOSTER FANS. | | | 7) REFER TO SECTION 304.11 GUARDS | | | 8) REFER TO SECTION 301.12 WIND RESISTANCE FOR | | | EQUIPMENT | | | ON THE ROOF. 2010 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|