| Plan Review Notes For Permit 15020401 |
| Permit Number |
15020401 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-12 11:08:17 | BUILDING PLAN REVIEW | | | PERMIT: 15020401 | | | ADD: 301 53RD ST UNIT # B | | | CONT: BESA CONSTRUCTION | | | TEL: (954)605-3399 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: | | | ACTION: DENIED | | | | | | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 1.1NOTE THE MEAN ROOF HEIGHT IS NOT GIVEN. | | | 1.2 UNIT SIZE OF SLIDING DOOR UNIT UNKNOWN. | | | 1.3) THE PRODUCT APPROVAL 12-0821.16 SHEET 7 OF 16 THE | | | GLAZING TYPE IS NOT IDENTIFIED NOR IS THE SILL HEIGHT, | | | STANDARD OR HIGH RISE SILL. PLEASE CIRCLE THE GLAZING | | | TYPE, SILL AND DIMENSIONS OF EACH DOOR IN THE UNIT, | | | THIS WILL GIVE THE PRESSURES THIS UNIT IS GOOD FOR. | | | THIS JOBSITE IS LOCATED IN A "D" WIND EXPOSURE SO THE | | | PRESSURES WILL HAVE MULTIPLIERS ONCE THE MEAN ROOF | | | HEIGHT IS KNOWN. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|