Plan Review Notes
Plan Review Notes For Permit 15020227
Permit Number 15020227
Review Stop E
Sequence Number 2
Notes
Date Text
2015-04-22 09:00:484/22/2015
 PROJECT: 235 BELMONTE
 PERMIT#: 15020227
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE THE LOCATION ON THE BUILDING(S) ALL
 ELECTRICAL PANELS, ELECTRICAL SERVICE ENTANCE
 SWITCHGEAR AND EQUIPMENT SUCH AS DISCONNECTS FOR A/C
 EQUIPMENT, WATER HEATERS, POOL EQUIPMENT, IRRIGATION
 EQUIPMENT, GATE CONTROLLERS, ETC...
  
 2) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT
 FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING
 OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS
 SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
  
 3) PROVIDE A GFI RECEPTACLE AT AN ACCESSIBLE LOCATION
 WITHIN SIGHT OF A/C EQUIPMENT.. NEC 210.63 NEC 210.8
  
 4) VERIFY LUMINAIRES IN CLOTHES CLOSETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC
 410.16(A) AND (B).
  
 5) VERIFY SPACING AS REQUIRED. SEE NEC 210.52(A)(1)
 THROUGH (A)(3). AND NEC 210.52(C)(1)
  
 6) VERIFY ALL HABITABLE ROOMS HAVE A SWITCHED LIGHTING
 OUTLET. SEE NEC 210.70. PLEASE NOTE A DUPLEX RECEPTACLE
 THAT IS SWITCHED ENTIRELY AND IS NOT FED WITH A
 CONTINUOUS HOT FOR AT LEAST ONE HALF OF THE DEVICE,
 DOES NOT COUNT AS ONE OF THE OUTLETS REQUIRED IN NEC
 210.70
  
 7) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST
 HAVE A RECEPTACLE OUTLET GFCI PROTECTED. NEC
 210.52(E)(3).
  
 8) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATORS. ATS, NG FUEL SYSTEM, FIRE
 ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]