| Date |
Text |
| 2015-04-17 14:29:17 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ONE SET OF THE PLANS IS MISSING SETS A-20, A-21 AND |
| | A-22. TWO COMPLETE SETS OF PLANS ARE REQUIRED. FBC |
| | 107.1 |
| | |
| | 2) A PRODUCT APPROVAL NOA NO. 12-0612.15 WAS SUBMITTED |
| | FOR EXTERIOR DOORS. IT IS FOR FIBERGLASS DOORS WITH |
| | SIDELITES WITH A OXX OR XXO CONFIGURATION AND A MAXIMUM |
| | FRAME WITDTH OF 108-1/2". THERE ARE NOT ANY DOORS LIKE |
| | THIS SPECIFIED ON THE PLANS. THE DOOR SCHEDULE |
| | SPECIFIES METAL DOORS. THERE ARE SINGLE AND DOUBLE |
| | FRENCH DOORS AND DOUBLE FRENCH DOORS WITH SIDELITES ON |
| | BOTH SIDES ON THE PLANS. |
| | |
| | 3) SUBMIT TWO SETS OF PRODUCT APPROVALS WITH |
| | INSTALLATION INSTRUCTIONS AND DESIGN WIND LOAD |
| | PRESSURES FOR THE CLAY BARREL ROOF TILE AS REQUIRED BY |
| | DCA RULE 9N-3. SPECIFY WHICH ONE OF THE ATTACHMENT |
| | METHODS WITH ADEQUATE UPLIFT RESISTANCE THAT ARE LISTED |
| | IN THE PRODUCT APPROVAL WILL BE USED. IF A ROOF TILE |
| | ADHESIVE IS TO BE USED, THEN SUBMIT TWO COPIES OF IT'S |
| | PRODUCT APPROVALS. FBC 107.2.1 AND FBC-R301.1 |
| | |
| | 4) ONE SET OF PRODUCT APPROVALS WERE SUBMITTED FOR |
| | SEALOFLEX ROOF SYSTEMS FOR CONCRETE (NOA NO. |
| | 12-0418.04), ONE FOR SEALOFLEX WATERPROOFING SYSTEM FOR |
| | CONCRETE (NOA NO.10-0608.04) AND ONE FOR SEALOFLEX |
| | WATERPROOFING SYSTEM FOR LIGHTWEIGHT CONCRETE (NOA |
| | NO.10-0608.03). SPECIFY WHERE EACH WILL BE INSTALLED |
| | AND INDICATE THE SPECIFIC ASSEMBLY AND ITS DESIGN |
| | PRESSURE. FBC 107.2.1 AND FBC-R301.1 |