Plan Review Notes
Plan Review Notes For Permit 15020227
Permit Number 15020227
Review Stop G
Sequence Number 1
Notes
Date Text
2015-02-11 11:21:491) INDICATE ON THE PLAN IF THE FIREPLACE IS GAS OR WOOD
 BURNING. IF IT IS GAS, THE BTU LOAD SHALL BE INCLUDED
 ON THE GAS DRAWING. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2) PLANS SHOW A FUTURE GENERATOR. INDICATE ON THE PLAN
 IF THE GENERATOR WILL BE CONNECTED TO THE NATURAL GAS
 SYSTEM. IF SO IT SHALL BE INCLUDED ON THE GAS RISER.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 3) SHOW THE LOCATION OF THE GAS METER ON THE PLANS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SUBMIT MANUF. SPECIFICATION SHEETS/INSTALLATION
 MANUAL FOR ALL APPLIANCES FOR REVIEW. APPLIANCES SHALL
 BE LISTED PER 2010 FBCR SEC.G2404.3.WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 5) SUBMIT A GAS PLAN SHOWING THE LOCATION OF THE PE GAS
 PIPE.PE PIPE SHALL BE INSTALLED OUTDOORS UNDERGROUND
 ONLY PER THE FBCR G2415.15.1. IT APPEARS THAT THE PE
 PIPE MAY BE RUNNING UNDER THE BUILDING SLAB.
 6) THE CSST LINE TO THE COOKTOP SHALL BE A MIN. OF 1"
 PER THE 2010 FBCR TABLE G 2413.4 (5) FOR A DEVELOPED
 LENGTH OF 40 FT.
 7) SHOW THE CORRESPONDING EHD FOR ALL CSST PIPE SIZES
 PER 2010 FBCR TABLE G 2413.4 (5).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  