| Plan Review Notes For Permit 15020227 |
| Permit Number |
15020227 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-11 11:21:49 | 1) INDICATE ON THE PLAN IF THE FIREPLACE IS GAS OR WOOD | | | BURNING. IF IT IS GAS, THE BTU LOAD SHALL BE INCLUDED | | | ON THE GAS DRAWING. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 2) PLANS SHOW A FUTURE GENERATOR. INDICATE ON THE PLAN | | | IF THE GENERATOR WILL BE CONNECTED TO THE NATURAL GAS | | | SYSTEM. IF SO IT SHALL BE INCLUDED ON THE GAS RISER.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 3) SHOW THE LOCATION OF THE GAS METER ON THE PLANS.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 4) SUBMIT MANUF. SPECIFICATION SHEETS/INSTALLATION | | | MANUAL FOR ALL APPLIANCES FOR REVIEW. APPLIANCES SHALL | | | BE LISTED PER 2010 FBCR SEC.G2404.3.WPB AMEND. TO 2010 | | | FBC SEC. 107.2.1. | | | 5) SUBMIT A GAS PLAN SHOWING THE LOCATION OF THE PE GAS | | | PIPE.PE PIPE SHALL BE INSTALLED OUTDOORS UNDERGROUND | | | ONLY PER THE FBCR G2415.15.1. IT APPEARS THAT THE PE | | | PIPE MAY BE RUNNING UNDER THE BUILDING SLAB. | | | 6) THE CSST LINE TO THE COOKTOP SHALL BE A MIN. OF 1" | | | PER THE 2010 FBCR TABLE G 2413.4 (5) FOR A DEVELOPED | | | LENGTH OF 40 FT. | | | 7) SHOW THE CORRESPONDING EHD FOR ALL CSST PIPE SIZES | | | PER 2010 FBCR TABLE G 2413.4 (5). | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|