| 2015-03-16 11:31:51 | 3/16/2015 |
| | PROJECT: 235 BELMONTE |
| | PERMIT#: 15020227 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FBC-R 314, 315 |
| | ADD SMOKE DETECTORS AS REQUIRED FOR THE POOL HOUSE AND |
| | MAIN HOUSE SLEEPING ROOMS AND ADDITIONAL LANDINGS 1ST |
| | AND 2ND FLS . |
| | |
| | 2) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLANS |
| | CORREPSPONDING WITH THE ELECTRICAL PANEL SCHEDULES OCPD |
| | AND WIRE SIZES |
| | |
| | 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 4) ALL EXISTING AREAS NOT INVOLVED IN THE CURRENT SCOPE |
| | OF WORK INDICATED ON THESE DESIGN DOCUMENTS SHALL BE IN |
| | COMPLIANCE WITH THE FBC- EXISTING CHAPTERS, 6,7,AND 8. |
| | |
| | 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR GENERATORS. ATS, NG FUEL SYSTEM, FIRE |
| | ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV, |
| | AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |