Plan Review Notes
Plan Review Notes For Permit 15020227
Permit Number 15020227
Review Stop E
Sequence Number 1
Notes
Date Text
2015-03-16 11:31:513/16/2015
 PROJECT: 235 BELMONTE
 PERMIT#: 15020227
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FBC-R 314, 315
 ADD SMOKE DETECTORS AS REQUIRED FOR THE POOL HOUSE AND
 MAIN HOUSE SLEEPING ROOMS AND ADDITIONAL LANDINGS 1ST
 AND 2ND FLS .
  
 2) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLANS
 CORREPSPONDING WITH THE ELECTRICAL PANEL SCHEDULES OCPD
 AND WIRE SIZES
  
 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 4) ALL EXISTING AREAS NOT INVOLVED IN THE CURRENT SCOPE
 OF WORK INDICATED ON THESE DESIGN DOCUMENTS SHALL BE IN
 COMPLIANCE WITH THE FBC- EXISTING CHAPTERS, 6,7,AND 8.
  
 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATORS. ATS, NG FUEL SYSTEM, FIRE
 ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  