Plan Review Notes
Plan Review Notes For Permit 15020227
Permit Number 15020227
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-17 11:04:33PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE STRUCTURAL DETAILS FOR THE PROPOSED PERGOLA
 AT THE POOL HOUSE. FBC-R 301.1
  
 2) PROVIDE STRUCTURAL DRAWINGS FOR THE ARCHED BEAMS
 THAT SHOW THE STEEL PLACEMENT. FBC 107.2.1
  
 3) IN THE FLAT BEAM SCHEDULE ON SHEET S-21, THERE ARE
 TWO FB-1 MARKS LISTED. IT APPEARS THAT THE SECOND ONE
 SHOULD BE FB-2. FBC 107.2.1
  
 4) PROVIDE SCUPPER SIZING CALCULATIONS AND SPECIFY THE
 SIZES OF THE ROOF SCUPPERS AND OVERFLOW SCUPPERS FOR
 THE NEW POOL HOUSE LOW SLOPE ROOF ON THE PLANS. FBC-R
 903.4
  
 5) R318.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES, IRRIGATION/SPRINKLER SYSTEM RISERS
 FOR SPRAY HEADS, AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 6) SHOW COMPLIANCE WITH FBC 807.1 FOR ATTIC ACCESS.
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION
 SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT
 EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL
 HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL
 HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING
 FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING
 MEMBERS.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. WHEN LOCATED IN A WALL, THE OPENING SHALL BE
 A MINIMUM OF 22 INCHES WIDE BY 30 INCHES HIGH. WHEN THE
 ACCESS IS LOCATED IN A CEILING, MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE 30 INCHES (762 MM)
 AT SOME POINT ABOVE THE ACCESS MEASURED VERTICALLY FROM
 THE BOTTOM OF CEILING FRAMING MEMBERS. SEE SECTION
 M1305.1.3 FOR ACCESS REQUIREMENTS WHERE MECHANICAL
 EQUIPMENT IS LOCATED IN ATTICS.
  
 7) ON SHEET S-20, THE INCORRECT EDITIONS OF ACI AND TMS
 ARE REFERENCED. THE 2008 EDITIONS ARE THE ONES
 REFERENCED IN CHAPTER 43 OF THE 2010 FBC.
  
 8) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBC-R316
  
 9) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
 -THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT
 APPROVAL WEBSITE.
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
 -THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT
 APPROVAL WEBSITE.
 HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 10) THE FOLLOWING CONNECTORS DO NOT HAVE THEIR PRODUCT
 APPROVAL NUMBERS LISTED ON THE PLANS AND WILL REQUIRE
 PRODUCT APPROVALS TO BE SUBMITTED IF THEY ARE NOT
 PROVIDED ON THE PLANS: HUS 210, THA 413 AND LTT19.
  
 11) SHOP DRAWING SUBMITTALS WILL BE REQUIRED FOR THE
 METAL BALCONY GUARDS. FBC-R 312 & R 301.5
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  